Chapter 5 - Parameter List
5-6
5.3 Function 2 Group [FU2]
Keypad Display
Setting Range
Code
Description
LCD
7-Segment
LCD
7-Segment
Units
Factory
Default
Adj.
During
Run
Page
FU2-00
Jump to desired code #
Jump code
Not displayed
1 to 94
Not available
1
1
Yes
6-2
FU2-01
Previous Fault History 1
Last trip-1
01
FU2-02
Previous Fault History 2
Last trip-2
02
FU2-03
Previous Fault History 3
Last trip-3
03
FU2-04
Previous Fault History 4
Last trip-4
04
FU2-05
Previous Fault History 5
Last trip-5
05
By pressing [PROG] and [
▲
] key,
the frequency, current, and
operational status at the time of fault
can be seen.
- None -
No 0
FU2-06
Erase Fault History
Erase trips
06
Yes 1
- No Yes
6-2
FU2-07
Dwell Frequency
Dwell freq
07
FU1-22 to FU1-20
0.01
5.00 [Hz]
No
FU2-08
Dwell Time
Dwell time
08
0 to 10 [sec]
0.1
0.0 [sec]
No
6-2
No 0
FU2-10
Frequency Jump
Selection
Jump freq
10
Yes 1
- No No
FU2-11
17
Jump Frequency 1 Low
Jump lo 1
11
FU1-22 to FU2-12
0.01 10.00 [Hz]
No
FU2-12
Jump Frequency 1 High
Jump Hi 1
12
FU2-11 to FU1-20
0.01 15.00 [Hz]
No
FU2-13
Jump Frequency 2 Low
Jump lo 2
13
FU1-22 to FU2-14
0.01 20.00 [Hz]
No
FU2-14
Jump Frequency 2 High
Jump Hi 2
14
FU2-13 to FU1-20
0.01 25.00 [Hz]
No
FU2-15
Jump Frequency 3 Low
Jump lo 3
15
FU1-22 to FU2-16
0.01 30.00 [Hz]
No
FU2-16
Jump Frequency 3 High
Jump Hi 3
16
FU2-15 to FU1-20
0.01 35.00 [Hz]
No
6-2
FU2-17
Start Curve for S-Curve
Accel/Dedel Pattern
Start Curve
17
1 to 100 [%]
1
40%
No
FU2-18
End Curve for S-Curve
Accel/Dedel Pattern
End Curve
18
1 to 100 [%]
1
40%
No
6-2
FU2-19
Input/Output Phase Loss
Protection
Trip select
19
00 to 11
(Bit Set)
- 00 Yes
6-2
No 0
FU2-20
Power ON Start Selection
Power-on run
20
Yes 1
- No Yes
6-2
No 0
FU2-21
Restart after Fault Reset
RST restart
21
Yes 1
- No Yes
6-2
FU2-22
Speed Search Selection
Speed Search
22
0000 to 1111
(Bit Set)
- 0000 No
FU2-23
Current Limit Level
During Speed Search
SS Sup-Curr
23
80 to 200 [%]
1
100 [%]
Yes
FU2-24
P Gain
During Speed Search
SS P-gain
24
0 to 30000
1
100
Yes
FU2-25
I Gain
During speed search
SS I-gain
25
0 to 30000
1
1000
Yes
6-2
FU2-26
Number of Auto Restart
Attempt
Retry number
26
0 to 10
1
0
Yes
6-2
17
Code FU2-11 through FU2-16 appears only when FU2-10 is set to ‘Yes’.
Summary of Contents for 30 HP30
Page 6: ......
Page 12: ......
Page 16: ...Chapter 1 Installation 1 4 BLANK ...
Page 18: ...Chapter 1 Installation 1 6 BLANK ...
Page 28: ...Chapter 1 Installation 1 16 Notes ...
Page 39: ...Chapter 2 Operation 2 11 Notes ...
Page 40: ......
Page 46: ......
Page 60: ...Chapter 4 Operation Examples 4 14 Notes ...
Page 83: ...Chapter 5 Parameter List 5 23 Notes ...
Page 84: ......
Page 92: ...Chapter 6 Parameter Description DRV 6 8 Notes ...
Page 105: ......
Page 106: ...Chapter 6 Parameter description FU1 6 14 Notes ...
Page 126: ...Chapter 6 Parameter Description FU2 6 34 Notes ...
Page 144: ...Chapter 6 Parameter Description I O 6 52 Notes ...
Page 162: ......
Page 188: ...Chapter 7 Options 7 26 Type 1 Max 400 Watt Type 2 Max 600 Watt A ...
Page 189: ...Chapter 7 Options 7 27 Type 3 ...
Page 194: ......
Page 204: ......
Page 210: ......