Chapter 5 - Parameter List
5-20
Keypad Display
Setting Range
Code
Description
LCD
7-Segment
LCD
7-Segment
Units
Factory
Default
Adj.
During
Run
Page
APP-02
27
Traverse Amplitude
Trv. Amp
02
0.0 to 20.0 [%]
0.1
0.0 [%]
Yes
6-2
APP-03
Traverse Scramble
Amplitude
Trv. Scr
03
0.0 to 50.0 [%]
0.1
0.0 [%]
Yes
6-2
APP-04
Traverse Accel Time
Trv Acc Time
04
0 to 6000 [sec]
0.1
2.0 [sec]
Yes
6-2
APP-05
Traverse Decel Time
Trv Dec Time
05
0 to 6000 [sec]
0.1
3.0 [sec]
Yes
6-2
APP-06
Traverse Offset (Hi)
Setting
Trv Off Hi
06
0.0 to 20.0 [%]
0.1
0.0 [%]
Yes
6-2
APP-07
Traverse Offset (Lo)
Setting
Trv Off Lo
07
0.0 to 20.0 [%]
0.1
0.0 [%]
Yes
6-2
APP-08
28
Running Auxiliary Motor
Number Display
Aux Mot Run
08
- -
-
-
6-2
APP-09
Starting Aux. Motor
Selection
Starting Aux
09
1 to 4
1
1
Yes
6-2
APP-10
Operation Time Display
on Auto Change
Auto Op Time
10
- -
-
-
6-2
APP-11
Start Frequency of Aux.
Motor 1
Start freq 1
11
0 to FU1-20
0.01 49.99 [Hz] Yes
APP-12
Start Frequency of Aux.
Motor 2
Start freq 2
12
0 to FU1-20
0.01 49.99 [Hz] Yes
APP-13
Start Frequency of Aux.
Motor 3
Start freq 3
13
0 to FU1-20
0.01 49.99 [Hz] Yes
APP-14
Start Frequency of Aux.
Motor 4
Start freq 4
14
0 to FU1-20
0.01 49.99 [Hz] Yes
6-2
APP-15
Stop Frequency of Aux.
Motor 1
Stop freq 1
15
0 to FU1-20
0.01 15.00 [Hz] Yes
APP-16
Stop Frequency of Aux.
Motor 2
Stop freq 2
16
0 to FU1-20
0.01 15.00 [Hz] Yes
APP-17
Stop Frequency of Aux.
Motor 3
Stop freq 3
17
0 to FU1-20
0.01 15.00 [Hz]] Yes
APP-18
Stop Frequency of Aux.
Motor 4
Stop freq 4
18
0 to FU1-20
0.01 15.00 [Hz] Yes
6-2
APP-19
Delay Time before
Operating Aux Motor
Aux start DT
19
0 to 9999 [sec]
0.1
60.0 [sec]
Yes
APP-20
Delay Time before
Stopping Aux Motor
Aux stop DT
20
0 to 9999 [sec]
0.1
60.0 [sec]
Yes
6-2
APP-21
The Number of Aux Motor
Nbr Aux’s
21
0 to 4
1
4
Yes
6-2
No 0
APP-22
PID Bypass Selection
Regul Bypass
22
Yes 1
- No Yes
6-2
APP-23
Sleep Delay Time
Sleep Delay
23
0 to 9999 [sec]
0.1
60.0 [sec]
Yes
6-2
APP-24
Sleep Frequency
Sleep Freq
24
0 to FU1-20
0.01 19.00 [Hz] Yes
6-2
27
Code APP-02 through APP-07 appears only when APP-01 is set to ‘Traverse’.
28
Code APP-08 through APP-31 appears only when APP-01 is set to ‘MMC’.
Summary of Contents for 30 HP30
Page 6: ......
Page 12: ......
Page 16: ...Chapter 1 Installation 1 4 BLANK ...
Page 18: ...Chapter 1 Installation 1 6 BLANK ...
Page 28: ...Chapter 1 Installation 1 16 Notes ...
Page 39: ...Chapter 2 Operation 2 11 Notes ...
Page 40: ......
Page 46: ......
Page 60: ...Chapter 4 Operation Examples 4 14 Notes ...
Page 83: ...Chapter 5 Parameter List 5 23 Notes ...
Page 84: ......
Page 92: ...Chapter 6 Parameter Description DRV 6 8 Notes ...
Page 105: ......
Page 106: ...Chapter 6 Parameter description FU1 6 14 Notes ...
Page 126: ...Chapter 6 Parameter Description FU2 6 34 Notes ...
Page 144: ...Chapter 6 Parameter Description I O 6 52 Notes ...
Page 162: ......
Page 188: ...Chapter 7 Options 7 26 Type 1 Max 400 Watt Type 2 Max 600 Watt A ...
Page 189: ...Chapter 7 Options 7 27 Type 3 ...
Page 194: ......
Page 204: ......
Page 210: ......