10.  BYPASS DIODES AND BLOCKING DIODES  

 
Partial shading of an individual Module can cause a reverse voltage across the shaded SPV Module. Current is then 
forced through the shaded area by the other Modules. 
 
When a bypass diode is wired in parallel with the series string, the forced current will flow through the diode and 
bypass the shaded SPV Module, thereby minimizing Module heating and array current losses. 
 
In system utilizing a battery, blocking diodes are typically placed between the battery and the SPV Module output to 
prevent battery discharge at night. 
 
Diodes that are used as blocking diodes must: Have a Rated Average Forward Current [I

F(AV)

above

 maximum 

system current at highest Module operating temperature. Have a Rated Repetitive Peak Reverse Voltage [V

RRM

above

 maximum system voltage at lowest Module operating temperature. 

 
11. WARNING AND NOTES 

 
The SPV Modules generate electricity when exposed to light. Array of many Modules can cause lethal electrical 
shock and burn hazards. Only authorized and trained personnel should have access to these Modules. To reduce the 
risk of electrical shock or burns, modules maybe covered with an opaque material during installation to avoid 
electrical shocks or burns. Do not touch live terminals with bare hands. Use insulated tools for electrical connections. 
 
Use appropriate methods to mount SPV Modules. Fall of Modules from high place will cause death, injury or 
damage. 
The SPV Module has a pair of male and female waterproof connectors. For a series electrical connection, connect 
positive (+) connector of first SPV Module to negative (-) connector of the following Module. 
Do not short the positive and the negative. Do not disconnect under load. Be sure connectors have no gap between 
the insulators. In case there is a gap, a fire and/or an electrical shock may occur.  
 
 
NOTES: 
 
(1) Artificially concentrated sunlight shall not be directed on the SPV Module. The rated electrical characteristics are 
within 10 percent of measured values under standard test conditions (Irradiance of 1000W/m

2

, AM 1.5 spectrum, and 

cell temperature of 25°C). 
(2) Under normal conditions, a solar photovoltaic Module is likely to experience conditions that produce more 
current and/or voltage than reported at standard test conditions. Accordingly the value of Isc and Voc marked on this 
Module should be multiplied by a factor of 1.25 when determining component voltage ratings, conductor current 
ratings, fuse sizes, and sizes of controls connected to the SPV output.  
 (3) Details for wiring in accordance with the local regulations. 
(4) If you install modules in parallel electrically, each module (or series string of modules so connected) shall be 
provided with the maximum series fuse as specified. 
 
 
 

Summary of Contents for CNPV-PS-M-S0010-IEC

Page 1: ...IEC INSTALLATION INSTRUCTION AND MAINTENANCE MANUAL FOR CRYSTALLINE SOLAR PV MODULE...

Page 2: ...a range of sizes designed to meet the requirements of the most demanding energy and power users worldwide 2 POWER MODULE CNPV Solar Photovoltaic Modules consist of a series of electrically interconne...

Page 3: ...ltaic Modules especially during the winter months when the arc of the sun is lowest over the horizon Shading causes loss of output even though the factory fitted bypass diodes of the SPV Module will m...

Page 4: ...ropriate local and civil codes prior to installation CNPV SPV Modules can be mounted as following method Figure 2 Mounting Method a and b a Using corrosion proof screws M8 on the existing installing h...

Page 5: ...surface of the building wall or roof Clearance between the Module frames and surface of the wall or roof is required to prevent wiring damage and to allow air to circulate behind the Module The recom...

Page 6: ...ould have access to these Modules To reduce the risk of electrical shock or burns modules maybe covered with an opaque material during installation to avoid electrical shocks or burns Do not touch liv...

Page 7: ...e considered to meet the requirements for Safety class II 14 MAINTENANCE Under most weather conditions normal rainfall is sufficient to keep the SPV Module glass surface clean If dirt build up becomes...

Page 8: ...35 15 160 34 5 4 65 43 0 5 15 IEC61215 IEC61730 1000VDC 10 17 2 CNPV 165M 165 35 2 4 70 43 4 5 20 17 2 CNPV 170M 170 35 8 4 75 43 8 5 25 17 2 CNPV 175M 175 36 6 4 80 44 2 5 30 17 2 CNPV 180M 180 37 2...

Page 9: ...4 225 27 8 8 10 33 8 8 60 23 3 CNPV 230M 54 230 28 0 8 20 33 9 8 70 23 3 CNPV 235M 54 235 28 3 8 30 34 0 8 80 23 3 CNPV 240M 54 240 28 7 8 35 34 1 8 85 23 3 60pcs 156 156mm SPV Module Mono Crystalline...

Page 10: ...10 33 8 8 60 23 3 CNPV 230MB 54 230 28 0 8 20 33 9 8 70 23 3 CNPV 235MB 54 235 28 3 8 30 34 0 8 80 23 3 CNPV 240MB 54 240 28 7 8 35 34 1 8 85 23 3 60pcs 156 156mm SPV Module Black Mono Crystalline Si...

Page 11: ...4 1 8 50 23 3 CNPV 230P 54 230 28 4 8 10 34 3 8 55 23 3 CNPV 235P 54 235 28 6 8 20 34 5 8 65 23 3 60pcs 156 156mm SPV Module Poly Crystalline Silicon CNPV 210P 1650 992 35 20 210 29 2 7 20 36 4 7 80 2...

Page 12: ...CNPV 230PB 54 230 28 4 8 10 34 3 8 55 23 3 CNPV 235PB 54 235 28 6 8 20 34 5 8 65 23 3 60pcs 156 156mm SPV Module Black Poly Crystalline Silicon CNPV 210PB 1650 992 35 20 210 29 2 7 20 36 4 7 80 20 21...

Page 13: ...86 546 7795555 Fax 86 546 7795777 4 9 12 INSTALLING HOLE 1581 2 948 7 5 4 4 12 DRAIN HOLE 2 4 GROUNDING HOLE GROUNDING MARKING 809 2 4 4 6 DRAIN HOLE 4 4 4 DRAIN HOLE 316 5 316 5 Section A A magnified...

Page 14: ...CE 1202 4 12 DRAIN HOLE 8 9 12 INSTALLING HOLE 2 4 GROUNDING HOLE 992 2 702 For normal installation 1200 Typical GROUNDING MARKING 942 4 4 5 4 DRAIN HOLE 140 140 1482 2 390 390 For High wind and snow...

Page 15: ...l 86 546 7795555 Fax 86 546 7795777 1 9 35 35 1 8 1 5 990 4 12 DRAIN HOLE 8 9 12 INSTALLING HOLE 2 4 GROUNDING HOLE 992 2 Section A A magnified 941 4 4 5 4 DRAIN HOLE 330 330 1200 Typical 1650 2 11 GR...

Page 16: ...86 546 7795555 Fax 86 546 7795777 1965 2 1177 941 4 R2 25 4 DRAIN HOLE 2 4 GROUNDING HOLES 4 9 12 INSTALLING HOLE GROUNDING MARKING 4 R6 DRAIN HOLE Section A A magnified 11 394 394 35 40 2 0 992 2 120...

Reviews: