11
Message Buffers
The information in this section is meant to supplement the discussion on
message buffers in Chapter 2 of the LonWorks Router User’s Guide. An
additional source of information on message buffers can be found in
Chapter 6 of the Neuron C Programmer’s Guide.
The buffer types described in the LonWorks Router User’s Guide are actu-
ally a subset of the buffers available on each side of the RTR-10 Router
Core Module. The complete list of buffer types, which are the same as
those available on any Neuron Chip, is given below:
•
Receive Transaction Buffers
•
Transmit Transaction Buffers
•
Input Application Buffers
•
Output Application Buffers
•
Input Network Buffers (referred to as “Input Buffers” in the LonWorks
Router User’s Guide)
•
Output Network Buffers (referred to as “Normal Output Buffers” or
“Non-Priority Output Buffers” in the LonWorks Router User’s Guide)
•
Priority Output Application Buffers
•
Priority Output Network Buffers (referred to as “Priority Output
Buffers” in the LonWorks Router User’s Guide)
The buffer types not mentioned in the LonWorks Router User’s Guide are
used only for network management messages sent to the RTR-10 Module.
The count and size of these buffers should never be changed or the RTR-
10 Module will not function correctly.
The maximum number of bytes available for the buffers in each side of
the RTR-10 Module is 1475. Of these bytes, 221 are reserved for the
Receive Transaction, Transmit Transaction, Input Application, Output
Application, and Priority Output Application Buffers. This leaves 1254
bytes available for the Input Network, Output Network, and Priority
Output Network Buffers. If the total number of bytes for these buffers
exceeds 1254, the ROUTER-LL will not function correctly.
The counts and sizes of message buffers in the ROUTER-LL are typically
configured in the network services tool and set when the router is
installed. The values for the counts and sizes of the buffers are restricted
by the RTR-10 firmware. The legal values are:
•
Count must be either 1, 2, 3, 5, 7, 11, 15, or 23.
•
Size must be either 42, 50, 66, 82, 114, 146, 210 or 255.