24
Appendix F: LonMaker Installation
This section describes the steps needed to install the ROUTER-LL into
your LonWorks network using Echelon’s LonMaker Installation Tool. See
the LonManager Profiler Users Guide (078-0022-01B, Echelon Corp.) and the
LonManager LonMaker Installation Tool Users Guide (078-0023-01B, Echelon
Corp.) for complete details on router installation.
Import the RIF files
From Profiler, import the RIF files supplied on the Companion Disk as
described in the Profiler documentation.
Define the IP Channel
From the Profiler Main window, select
Channel
Types
. Select
Create
to
open the Channel Type Create window, enter a name of your choice, and
then enter the following values:
Num Priorities:
0
Transceiver Type:
Special Purpose
Min Clock Rate:
10 MHz
Avg Packet Size:
15
Osc Accuracy:
200 ppm
Bit Rate:
[configurable] bps
Interface Rate:
1250 Kbps
Xcvr Controls Preamble:
Yes
General Purpose Data:
00 00 00 00 00 00 00
Alternate Bit Rate:
5000 bps
Wakeup Pin Dir:
Input
Select the
More...
button to set the Layer 1 Time Factors.
Preamble Length:
110 microsec
Receive Start Delay:
[configurable] microsec
Receive End Delay:
0 microsec
Indeterminate Time:
0 microsec
Minimum Interpacket:
0 microsec
Use Raw Data?
No
Raw Data
00 00 00 00 00
Select
OK
and then
Save
to create the new channel.
The Bit Rate
and
Receive Start Delay
parameters depend upon
the speed of your IP network. See Appendix B: Communications Parame-
ters
for guidelines on setting these values.