5  SYSTEM CONFIGURATION

5.1  Ethernet Connection

29

5

5

SYSTEM CONFIGURATION

5.1

Ethernet Connection

This section shows the system configuration when a code reader CF26 and a programmable controller are connected with an 
Ethernet.

For the settings of CC-Link IE Field Network Basic connection and SLMP scanner connection, configure the 
system using Ethernet.

Ethernet

Triggers are sent to a code reader, and character strings read by the code reader are received in a programmable controller 
via Ethernet.

USB cable

Programmable controller

Ethernet cable

Ethernet cable

Ethernet cable
(COGNEX product)

Code Reader CF26

100 V 

power supply

Switching 

hub

24 VDC 

power supply

Engineering tool, Profile, and

Code Reader setup tool

Breakout cable
(COGNEX product)

Summary of Contents for Mitsubishi Electric MELSENSOR CF26 Series

Page 1: ...6 User s Manual CF26 SR CF26 LR This product is designed and manufactured by Cognex Corporation Note that the warranty and general specifications of this product differ from that of programmable contr...

Page 2: ......

Page 3: ...micals to adhere Item Code reader Programmable controller product Example MELSEC iQ R series Free warranty period 18 months after delivery or 24 months after manufacture 36 months after delivery or 42...

Page 4: ...of conformance must be the judgment of the machinery manufacturer itself To meet the CE compliant conditions implement the following items Significant amount of noise on the power source may cause mal...

Page 5: ...the code reader be sure to touch an electric conductor such as grounded metal to discharge the static electricity from your body Otherwise damage or faulty operation of the code reader may occur Be su...

Page 6: ...orized modifications may void your warranty Changes or modifications not expressly approved by the party responsible for regulatory compliance could void the user s authority to operate the equipment...

Page 7: ...reader in Nuclear Power Plants and any other power plants operated by Power companies and or any other cases in which the public could be affected if any problem or fault occurs in the code reader Ra...

Page 8: ...maintenance and inspection and troubleshooting to use the code readers listed below Before using the product please read this manual and relevant manuals carefully and develop familiarity with the fun...

Page 9: ...s 21 3 6 I O Specifications 22 Image acquisition trigger 22 3 7 Cable Specifications 25 Ethernet cable COGNEX product 25 Breakout cable COGNEX product 26 CHAPTER 4 FUNCTIONS 27 4 1 Function List 27 CH...

Page 10: ...43 Connection example of an I O module 44 CHAPTER 7 INSTALLATION 46 7 1 Software Installation 46 7 2 Registration of a Profile 46 CHAPTER 8 MAINTENANCE AND INSPECTION 48 8 1 Cleaning a Code Reader CF...

Page 11: ...bookmarked Sample programs can be copied to an engineering tool Manual name manual number Description Available form Code Reader CF26 User s Manual SH 082092ENG this manual Describes the functions in...

Page 12: ...for SWnDND GXW2 and SWnDNC GXW2 n indicates its version GX Works2 corresponding to MELSOFT Navigator is the product later than GX Works2 Version 1 11M A configuration tool used for setting of MELSEC...

Page 13: ...inspection process and inventory control in a shipment process USB cable Programmable controller Ethernet cable Ethernet cable Ethernet cable COGNEX product Code Reader CF26 100 V power supply Switch...

Page 14: ...12 1 PRODUCT OVERVIEW MEMO...

Page 15: ...omponents The following shows the three main modules of a code reader CF26 No Name Description 1 Optics module Lens lights front cover 2 Main module Sensor CPU 3 I O connector module Power supply I O...

Page 16: ...CF26 No Name 1 Integrated lights 2 LED aimer guides 3 Mounting holes M3 3 5 mm 4 TRIG button 5 Power indicator 6 Registration status indicator 7 Read success fail indicator 8 Network status indicator...

Page 17: ...t Where in danger of organic solvents such as benzene thinner and alcohol or strong alkaline substances such as caustic soda to adhere Where subject to much vibration or shock Where in danger of liqui...

Page 18: ...supply 24 VDC 10 max 1 A LPS or NEC class 2 only Power consumption Max 5W Input 0 trigger Opto isolated image acquisition trigger input 1 Voltage ON 15 to 25 VDC standard 24 VDC OFF 0 to 5 VDC standar...

Page 19: ...ng shows the minimum code sizes that can be read in each working distance The following figure shows the field of view in horizontal direction and vertical direction Unit mm Working distance Minimum s...

Page 20: ...D code Minimum size for 2 D code 80 0 0508 2 mil 0 0508 2 mil 150 0 0508 2 mil 0 0762 3 mil 190 0 0508 2 mil 0 1016 4 mil 225 0 0762 3 mil 0 1016 4 mil 375 0 1016 4 mil 0 1778 7 mil 500 0 1524 6 mil 0...

Page 21: ...urn ON in order from the left according to the stage of the process No Indicator name Display specification 1 Power indicator Green Powered ON 2 Registration status indicator Green Code registered Yel...

Page 22: ...ages manually by setting the operation of the TRIG button The operation of the TRIG button can be set in DataMan Setup Tool The Inputs Outputs button the Basic tab the TRIG Button tab Item Description...

Page 23: ...ader when pressing the TUNE button can be set in DataMan Setup Tool The Inputs Outputs button the Basic tab the TUNE Button tab How to press Description Press one time The ON OFF status of LED aimer g...

Page 24: ...e started using a sink type device or source type device Sink type To trigger from the output of a sink type photodetector or programmable controller connect Input 0 of a breakout cable COGNEX product...

Page 25: ...negative side 0 VDC For a connection to which a 24 VDC power supply is connected when Output 0 to Output 3 are turned ON the outputs are pulled up to 21 VDC or more then a current flows to the extern...

Page 26: ...ler connect Output 0 to Output 3 of a breakout cable COGNEX product directly to the input terminals of the controller inputs When Output 0 to Output 3 are turned ON the input terminals are pulled down...

Page 27: ...Ethernet cable COGNEX product Ethernet cables COGNEX product are used for directly connecting a code reader CF26 to one device or connecting a code reader to multiple devices via a switching hub or a...

Page 28: ...les COGNEX products CCB PWRIO CCB PWRIO R and CCB M12X12FS 05 have different signal names and wire colors respectively Pin Number CCB PWRIO CCB PWRIO R CCB M12X12FS 05 Signal name Wire color Signal na...

Page 29: ...To set the code types and multi codes that can be read in a code reader Basic To select codes that can be read in a code reader CF26 The codes can be detected automatically from the read image Advanc...

Page 30: ...28 4 FUNCTIONS 4 1 Function List MEMO...

Page 31: ...Basic connection and SLMP scanner connection configure the system using Ethernet Ethernet Triggers are sent to a code reader and character strings read by the code reader are received in a programmab...

Page 32: ...characters read by the code reader are received in a programmable controller via Ethernet USB cable Programmable controller Ethernet cable Ethernet cable Ethernet cable COGNEX product Code Reader CF26...

Page 33: ...on module via RS 232 serial communication and the read character strings are registered in a code reader in advance The character strings of the read code are verified with the registered one When the...

Page 34: ...RS 232 serial communication and the read character strings are registered in a code reader in advance The character strings of the read code are verified with the registered one When they are matched...

Page 35: ...controller Required for using code readers Page 35 Modules Engineering tool profile Required for setting a programmable controller Page 35 Configuration tool Code reader setup tool Required for setti...

Page 36: ...f the products listed below is required as necessary Mounting bracket optional item Preparation of the brackets listed below is required according to the location where the brackets being attached Pro...

Page 37: ...rmware of a code reader CF26 needs to be updated to the version that supports DataMan Setup Tool For details on the firmware update refer to the How do I use the Update Firmware function on the DataMa...

Page 38: ...oduct that can be connected to a code reader CF26 Ethernet cable COGNEX product The following shows the Ethernet cables COGNEX product that can be connected to a code reader CF26 Model COGNEX model Re...

Page 39: ...a code reader CF26 be sure to touch an electric conductor such as grounded metal to discharge the static electricity from your body Otherwise damage or faulty operation of the code reader CF26 may oc...

Page 40: ...ompress the upper edge of the gasket to fix the module The surface of the gasket as shown below is the side where the I O connector module is attached Make sure that the gasket is properly fixed on th...

Page 41: ...ten the module loosely with two cap nuts In this case be careful not to tighten the cap nuts firmly with a T10 torx driver 7 When fastening the cap nut fix it with a torque of 0 12 N m Then install th...

Page 42: ...F26 This section shows the examples of installing a universal mounting bracket to a code reader CF26 Installing a code reader CF26 at the angle 15 can reduce reflections and improve performance Instal...

Page 43: ...o connect with their key aligned with the keyway of the connector on a code reader Do not force the connections or damage may occur When powering ON the system turn ON the power of the programmable co...

Page 44: ...ith their key aligned with the keyway of the connector on a code reader Do not force the connections or damage may occur When powering ON the system turn ON the power of the programmable controller fi...

Page 45: ...oduct and an RS 232 connector D sub 9 Pin as follows 2 TxD white and yellow to RD RxD 3 RxD brown to SD TxD In addition connect the RS 232 connector as follows ER DTR to DR DSR RS RTS to CS CTS 2 Conn...

Page 46: ...d terminals as follows 7 24 VDC red to a positive terminal 8 GND black to a negative terminal of the 24 VDC power supply Terminal name Breakout cable COGNEX product 24 VDC power supply X00 11 Output 0...

Page 47: ...black to a negative terminal of the 24 VDC power supply Terminal name Breakout cable COGNEX product 24 VDC power supply X00 11 Output 0 Blue X01 12 Output 1 Gray X02 1 Output 2 Yellow X03 4 Output 3 W...

Page 48: ...code reader CF26 by configuring communication settings registering a profile to an engineering tool is required A profile is data that stores information of a connected device such as a model name By...

Page 49: ...7 INSTALLATION 7 2 Registration of a Profile 47 7 MEMO...

Page 50: ...ter The air must be free of oil moisture or other contaminants that could remain on the lens cover These substances could remain on the glass and possibly degrade the image Do not touch the glass part...

Page 51: ...8 MAINTENANCE AND INSPECTION 8 3 Cleaning a Lens Cover 49 8 MEMO...

Page 52: ...NG 9 1 Error Checking Method If an error indicator turns ON or the code reader CF26 does not work properly check the error in the Device Log screen of DataMan Setup Tool System in the menu Device Log...

Page 53: ...9 TROUBLESHOOTING 9 1 Error Checking Method 51 9 MEMO...

Page 54: ...ference This section describes the precautions for machinery constructed with the MELSENSOR CF26 models to comply with the EMC Directive These precautions are based on the requirements of the EMC Dire...

Page 55: ...signal lines AC DC power I O power and AC I O unshielded lines 2kV DC I O analog and communication lines 1kV EN61000 4 5 Surge immunity Lightning surge is applied to power lines and signal lines AC p...

Page 56: ...rnal Dimensions Appendix 2 External Dimensions CF26 SR The following figures show the dimensions of a code reader CF26 SR 22 5mm 49 3mm 79 3mm 75 8mm 19 8mm 37mm M3 4 2x 25 9mm M3 4 4x 42 4mm 44mm 48...

Page 57: ...pendix 2 External Dimensions 55 A CF26 LR The following figures show the dimensions of a code reader CF26 LR 64 5mm 22 5mm 94 5mm 91mm M3 4 2x 25 9mm 35mm 37mm M3 4 2x M3 4 2x 30 1mm 42 4mm 44mm 48 5m...

Page 58: ...56 APPX Appendix 2 External Dimensions MEMO...

Page 59: ...APPX Appendix 2 External Dimensions 57 A MEMO...

Page 60: ...e Manual number Description June 2019 SH NA 082092ENG A First edition This manual confers no industrial property rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Cor...

Page 61: ...een avoided if functions or structures judged as necessary in the legal safety measures the user s device is subject to or as necessary by industry standards had been provided 4 Failure that could hav...

Page 62: ...Solutions VisionPro VisionView The following are trademarks of Cognex Corporation The Cognex logo 1DMax 3D Locate 3DMax BGAII CheckPoint Cognex VSoC CVC 1000 FFD iLearn In Sight design insignia with...

Page 63: ......

Page 64: ...ect to change without notice When exported from Japan this manual does not require application to the Ministry of Economy Trade and Industry for service transaction permission HEAD OFFICE TOKYO BUILDI...

Reviews: