Maxem is a control system that regulates the load of the charging station. Therefore, it can 
be  calculated  according to  the  NEN  1010 with  a  lower  equal  time  factor*.  Maxem  makes 
sure that the charging station is less loaded when there is more charge in the house. The 
charging station can therefore be fused to a value higher than normal, but not higher than 
the threshold value of the main power supply terminal. 

Power supply 

Charging station capacity Maximal fusing, charging station

3-phase 25A

3-phase 32A

3-phase 25A

3-phase 25A

3-phase 16A

3-phase 16A

3-phase 35A

3-phase 32A

3-phase 32A

1-phase 25A

1-phase 32A

1-phase 25A

1-fase 40A

1-fase 32A

1-fase 32A

*(NEN 1010:2015 722.311) The equal time factor is the ratio between the maximum simultaneous load of a 
group of electrical devices or consumers within a certain period and the sum of their individual maximal loads 
within the same period.

01 - Voorbereidingen vooraf

Feeding and fuse protection

Hang  Maxem  on  a  clean,  moisture-free  wall.  Use  the  supplied  mounting  plate  and 
screws for this. Take into account sufficient space around the Maxem.

01 - Mounting on the wall

Wiring at the bottom

70mm

20mm

20mm

20mm

10

11

A.

230V power supply from Maxem

Maxem measures the power supply as follows:
• 

Amperage: divisible current coils measure the current through the phase wires.

• 

Voltage: internal voltmeter in Maxem with the voltage from the 230V power supply.

For  a  correct  measurement  it  is  necessary  to  know  from  which  phase  Maxem  is  fed.  In 
Maxem it is standardly installed that the supply is on Phase 1 (L1). 

Summary of Contents for maxem

Page 1: ...Installation Manual E N E R G Y M A N A G E R ...

Page 2: ...nd intellectual property of Cohere Energy Solutions B V Material in this document may not be modified reproduced or copied in part or in whole without the explicit written consent of Cohere Energy Solutions B V Additional information is available upon request Maxem is a registered trademark of Cohere Energy Solutions B V S M A R T C H A R G I N G C O N T R O L L E R C H A R G E S M A R T E R Insta...

Page 3: ...ng ICU charging station 17 Option 4 3 Connecting Tesla Wall Connector 18 Option 4 4 Connecting EV Box charging station 20 05 Connecting Maxem 21 06 Commissioning 22 07 Telephone installation check 23 Annex 1 Troubleshooting 24 Annex 2 Setting MID kWh meter 27 Annex 3 Crimping RJ connectors 28 EC Declaration of Conformity 30 What is Maxem From the meter box Maxem measures the energy use in the hous...

Page 4: ...nector Product specifications 2x Tie wrap Specifications Dimensions 184 mm L x 167 mm W x 55 mm H Weight 700g Working temperature 10 C to 35 C Storage temperature 0 C to 60 C Maximal humidity 80 Protection class II double insulated Seal IP20 Working height 0 to 2 000 m EMC EN 61326 1 2013 EN 61000 3 2 61000 3 3 Safety EN61010 1 2010 EN61010 2 30 2010 Immunity EN 61326 1 2013 Overvoltage category 3...

Page 5: ...CES 01 Enclosure MH Vol mm mm Sheet Scale Cohere Date Drawn File reference Drawing name Material 17 02 2016 Maxem 4 Assembly A3 Stereo Design Zamenhofstraat 150 unit 336 1022AG Amsterdam Netherlands T 31 0 20 636 0671 M info stereodesign nl 0 2x45 or R 0 2 Ra 0 8 um Default length tolerances DIN 7168 20 Default angle tol Finish Default edges Roughness Tol 0 1 0 2 0 3 0 5 0 8 Dim 0 6 7 30 31 120 12...

Page 6: ...EN 1010 2015 722 311 The equal time factor is the ratio between the maximum simultaneous load of a group of electrical devices or consumers within a certain period and the sum of their individual maximal loads within the same period 01 Voorbereidingen vooraf Feeding and fuse protection Hang Maxem on a clean moisture free wall Use the supplied mounting plate and screws for this Take into account su...

Page 7: ...nd L3 in case of a 3 phase solar inverter Make sure the current coil s are connected in the right direction See right page Make sure the current coil s are connected in the right direction See right page A A 167 184 55 50 SECTION A A Client MH Cohere Drawn Drawing name Maxem 4 Assembly Stereo Design Zamenhofstraat 150 unit 336 1022AG Amste 0 2x45 or R 0 2 Ra 0 8 um Default length tolerances DIN 71...

Page 8: ...e RS485 cable to RS1 port on Maxem Connect this in such a way that it measures the output of the solar inverter A A 167 184 55 50 SECTION A A Client Rev nr 1 1 Units 1 2 CES 01 Enclosure MH Vol mm mm Sheet Scale Cohere Date Drawn File reference Drawing name Material 17 02 2016 Maxem 4 Assembly A3 Stereo Design Zamenhofstraat 150 unit 336 1022AG Amsterdam Netherlands T 31 0 20 636 0671 M info stere...

Page 9: ...tation These instructions can be found in the installation manual of the charging station Place a suitable UTP CAT5 or CAT6 cable from the charging station to Maxem and clench RJ45 connectors on both sides Connect the UTP cable to the Ethernet port of the charging station and the ETH port of Maxem It is possible to update the charging station firmware This can be done via ICU Connect as soon as th...

Page 10: ...D burns 5 secs green correctly set as Slave at start RJ10 4P4C See installation manual Tesla Wall Connector for more information Tab above Option 4 3 Connecting Tesla Wall Connector Install a circuit breaker or earth leakage circuit breaker for each charging station at the maximal power available See p 10 Follow the installation instructions of the charging station These instructions can be found ...

Page 11: ...g name Material 17 02 2016 Maxem 4 Assembly A3 Stereo Design Zamenhofstraat 150 unit 336 1022AG Amsterdam Netherlands T 31 0 20 636 0671 M info stereodesign nl 0 2x45 or R 0 2 Ra 0 8 um Default length tolerances DIN 7168 20 Default angle tol Finish Default edges Roughness Tol 0 1 0 2 0 3 0 5 0 8 Dim 0 6 7 30 31 120 121 400 401 1000 RS2 port for charging station Scheme EV Box controller Pin 1 Pin 2...

Page 12: ...g NOT OK Connection webportal OK Autoconfig OK Connection webportal NOT OK Maxem back to factory settings see chapter Troubleshooting Communication OK There is a connection but communication NOT OK Central LED indicator LED indicators for input output ports No connection detected A B LED indication blinks 3x LED indication blinks 4x LED indication blinks 2x LED indication blinks continuously LED i...

Page 13: ...he charging station is not detected or not correctly detected Turn off Maxem Wait for 10 seconds Then turn on Maxem If there is a charging station switch the group of the charging station off and on again The autoconfiguration will run again 24 25 Annex 1 Troubleshooting The car does not start during charging Perform a reboot of the group of the charging station in the meter box turn off the group...

Page 14: ...here is an active data connection with Maxem Location of the addressing function in the menu structure SET OK 1 2 3 Addressing example Number of devices Device type Standard addressing kWh meter Device Addressing Solar 001 Charging station 002 Heat pump 004 Devices Annex 2 Installation kWh meter Check the maximal charging capacity of the car For example the Tesla Model S needs a duo charger to cha...

Page 15: ...or Make sure that the cores are placed in the correct order For the RJ10 connector it is recommended to place 2 additional cores for pull relief C Make sure that the cores are inserted deep enough into the connector in order to have them firmly clamped D Place the connector with the inserted cable into the pliers Clench it in order to have the cores secured and exposed It may be necessary to clenc...

Page 16: ... Directive Hereby declare that the product Maxem Energy Manager 4 0 is in conformity with the applicable requirements of the following documents Emissions EN 61326 1 2013 EN 61000 3 2 2006 A1 2009 A2 2009 EN 61000 3 3 2008 Immunity EN 61326 1 2013 Safety EN 61010 1 2010 EN 61010 2 030 2010 EN 61010 2 023 Signee Date Place Signature Jan Willem Heinen CEO 1 August 2016 Amsterdam 30 31 Troubleshootin...

Page 17: ...C H A R G E S M A R T E R Willem de Zwijgerlaan 350 1055 RD Amsterdam The Netherlands 31 0 20 770 87 13 info cohere eu www cohere eu ...

Reviews: