DTB4848 Series Temperature Controller Settings
ABA Setup
Value Set Codes
Code
Description
A
ACTUAL SETTINGS
CnPt
Input Type
J
tPUn
Temperature Unit
F
tP-H
Scale Range Upper Limit (or default)
999.9
tP-L
Scale Range Lower Limit (or default)
-99.9
CtRL
Control Mode
onoF
S-HC
Control Action
CooL
ALA1
Alarm 1 Mode
5
ALA2
Alarm 2 Mode
5
ALA3
Alarm 3 Mode
1
SALA
System Alarm
OFF
CoSH
Communication Write Function
On
C-SL
Communication Format
ASCII
C-no
Communication Address
1
Bps
Communication Baud Rate
9600
LEN
Communication Data Length
8
Prty
Communication Parity Bit
Even
StoP
Communication Stop Bit
1
Value Set Codes
Code
Description
B
ACTUAL SETTINGS
r-S
Operation Mode
rUn
SP
Decimal point for SV
1.0
AL1H
Range Upper Limit
80.0
AL1L
Range Lower Limit
20.0
AL2H
High Temperature Limit
100.0
AL2L
Low Temperature Limit
15.0
AL3H
Deviation above SV Limit
30.0
AL3L
Deviation below SV Limit
7.0
LoC
Locks all values except SV
Loc2
Value Set Codes
Code
Description
A
ACTUAL SETTINGS
CtS
Set point Hyst/- Value
2.0
tPoF
Offset of actual to display temp
0.0
SV
Setpoint Value (°F)
60.0
Regulation Mode
Operation Mode
Initial Settings Mode
WKS_DTBsetting-Setup_ABA_0316.xlsx
1
4/5/2016