CKL_StartupChecklist-2-20ton_0213.docx
TYPICAL START-UP CHECK LIST
EQUIPMENT MODEL#
SERIAL#
OWNER NAME
PHONE#
ADDRESS
CITY
STATE
ZIP
INSTALLING CONTRACTOR
PHONE#
ADDRESS
CITY
STATE
ZIP
START-UP PERFORMED BY
PHONE#
* Designates Pre-Startup items. To be performed before Startup of system.
1.
*Manual referred to for details on installation and startup (IMPORTANT).
Yes No
2.
*Add additional information and notes on back of form, as needed.
Yes No
3.
*Is there any physical damage?
Yes No
a.
Will this prevent start-up?
Yes No
Description:
4.
*Unit is installed level as per the installation instructions.
Yes No
5.
*Electrical circuit protection has been sized & installed properly.
Yes No
6.
*Power supply agrees with the unit nameplate. V Ø Hz
Yes No
7.
*Electrical power wiring is installed properly.
Yes No
8.
*All terminals and plug assemblies are tight.
Yes No
9.
*Unit is grounded properly.
Yes No
10.
*Control voltage is appropriate per electrical drawing.
V
Yes No
11.
*All piping is connected properly, as appropriate.
Yes No
12.
*All chilled water valves are open, as appropriate.
Yes No
13.
*Crankcase heaters energized for 24 hours before start-up.
Yes No
14.
*Outdoor piping wrapped with electric heater tape, if necessary.
Yes No
15.
*Water loop volume greater than 6gal/ton.
Yes No
16.
*Proper fluid loop freeze protection provided to
˚F
a.
With type
mixture
% with
%
17.
Chilled water pump is operating with the correct rotation.
Yes No
18.
All air has been purged from the system.
Yes No
19.
Evaporator flow appropriate for capacity expected.(~3gpm/ton)
Yes No
20.
Check the pump(s) seals for any signs of leaking.
Yes No
21.
Measure the following under full load with clear refrigerant sight glass.
Yes No
Suction Pressure:
PSI
Ambient Temp:
˚F
Discharge Pressure:
PSI
Entering Fluid Temp:
˚F
Suction Line Temp:
˚F
Leaving Fluid Temp:
˚F
Superheat:
˚F
Set Value:
˚F
22.
Heat Exchanger models: If an extra heat exchanger is included with the chiller, ensure flow is
adjusted through the exchanger to achieve desired cooling:
Flowrate:
gpm Temp In:
˚F
Temp Out:
˚F
23.
Clean any strainers, as needed.
Yes No
24.
Operation Manual is given to customer.
Yes No
Summary of Contents for ACWC-180-EM-DR-LT-0-5