350155-CTG-C-0808
Johnson Controls Unitary Products
17
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
LOW CFM
COOLING PERFORMANCE DATA - LOW CFM 1-STAGE OPERATION
OUTDOOR UNIT MODEL NO.
AC8B036F1
INDOOR COIL MODEL NO.
FC62D + MV12D
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
750
800
850
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
25.4 26.8 27.2 29.7 32.8 25.9 27.0 27.3 30.1 33.0 26.4 27.2 27.5 30.4 33.2
S.C.
25.0 22.9 19.4 19.3 15.3 25.6 23.7 19.9 19.8 15.7 26.1 24.6 20.4 20.2 16.1
K.W.
1.00 0.99 0.99 0.96 0.93 0.99 0.98 0.98 0.95 0.92 0.97 0.97 0.97 0.94 0.91
75
T.C.
24.3 25.5 25.7 28.3 31.2 24.9 25.7 25.9 28.6 31.3 25.4 26.0 26.1 28.9 31.5
S.C.
24.0 22.3 18.8 18.7 14.8 24.6 23.1 19.4 19.2 15.3 25.1 23.8 19.9 19.7 15.7
K.W.
1.24 1.23 1.23 1.20 1.17 1.22 1.22 1.22 1.19 1.16 1.21 1.21 1.21 1.18 1.16
85
T.C.
23.3 24.2 24.3 26.9 29.5 23.8 24.5 24.5 27.2 29.7 24.3 24.7 24.8 27.5 29.8
S.C.
23.0 21.8 18.3 18.2 14.4 23.6 22.4 18.8 18.7 14.9 24.1 23.0 19.3 19.2 15.3
K.W.
1.47 1.47 1.47 1.44 1.41 1.46 1.46 1.46 1.43 1.41 1.45 1.45 1.45 1.42 1.40
95
T.C.
22.2 22.9 22.8 25.4 27.9 22.7 23.2 23.1 25.8 28.0 23.3 23.5 23.4 26.1 28.2
S.C.
22.0 21.2 17.7 17.6 14.0 22.6 21.7 18.2 18.2 14.5 23.1 22.2 18.8 18.7 14.9
K.W.
1.71 1.71 1.71 1.68 1.65 1.70 1.70 1.70 1.67 1.65 1.69 1.69 1.69 1.66 1.64
105
T.C.
20.8 21.3 21.0 23.6 26.0 21.3 21.7 21.3 23.8 26.1 21.9 22.1 21.5 24.1 26.2
S.C.
20.6 20.0 16.8 16.8 13.4 21.2 20.5 17.4 17.4 13.7 21.7 21.0 17.9 17.9 14.1
K.W.
2.03 2.03 2.03 2.01 1.98 2.02 2.02 2.02 2.00 1.97 2.00 2.01 2.01 1.99 1.97
115
T.C.
19.4 19.7 19.3 21.7 24.1 20.0 20.2 19.5 22.0 24.2 20.5 20.7 19.7 22.2 24.3
S.C.
19.2 18.8 16.0 16.1 12.8 19.8 19.3 16.6 16.6 13.0 20.4 19.8 17.1 17.1 13.3
K.W.
2.34 2.33 2.34 2.32 2.30 2.33 2.33 2.33 2.31 2.29 2.31 2.32 2.32 2.30 2.28
125
T.C.
18.0 18.2 17.5 19.9 22.2 18.6 18.8 17.7 20.1 22.3 19.1 19.3 18.0 20.4 22.4
S.C.
17.8 17.6 15.2 15.3 12.2 18.4 18.1 15.8 15.8 12.3 19.0 18.5 16.4 16.3 12.5
K.W.
2.65 2.64 2.65 2.63 2.62 2.64 2.64 2.65 2.63 2.61 2.62 2.63 2.64 2.62 2.60
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
AV36C
–
1.00 1.00 1.01
MV12B
FC/MC/PC43B
1.00 0.99 1.03
MV12B
FC/MC/PC43C
1.00 0.99 1.03
MV16C
FC/MC/PC43C
1.00 1.00 1.03
MV12D
FC/MC/PC48D
1.00 0.99 1.00
MV12D
UC48D
1.00 0.99 1.00
MV16C
FC/MC/PC48C
1.01 1.01 1.01
MV16C
FC/MC/PC48D
1.01 1.01 1.01
MV16C
UC48D
1.01 1.01 1.01
MV20D
FC/MC/PC48D
1.00 1.00 1.01
MV20D
UC48D
1.00 1.00 1.01
MV12D
FC/MC62D
1.00 1.00 1.00
MV20D
FC/MC62D
1.01 1.01 1.01
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
(F,L)C8V*A12
FC/MC/PC37A 0.99
0.99
1.03
(F,L)C9V*A12
FC/MC/PC37A 1.00
0.99
1.04
(F,L)C8V*B16
FC/MC/PC43B 0.99
0.99
1.02
(F,L)C8V*B16
FC/MC/PC43C 0.99
0.99
1.02
(F,L)C8V*C16
FC/MC/PC43C 0.96
0.96
1.00
(F,L)C8V*C20
FC/MC/PC43C 1.00
1.00
1.02
(F,L)C9(C,V)*B12
FC/MC/PC43B 1.00
0.99
1.03
(F,L)C9(C,V)*B12
FC/MC/PC43C 1.00
0.99
1.03
(F,L)C9(C,V)*C16
FC/MC/PC43C 1.00
1.00
1.01
(F,L)C9(C,V)*C20
FC/MC/PC43C 1.00
1.00
1.03
(F,L)C8V*C16
FC/MC/PC48C 0.96
0.96
0.98
(F,L)C8V*C16
FC/MC/PC48D 0.96
0.96
0.98
(F,L)C8V*C16
UC48D 0.96
0.96
0.98
(F,L)C8V*C20
FC/MC/PC48C 1.01
1.01
1.00
(F,L)C8V*C20
FC/MC/PC48D 1.01
1.01
1.00
(F,L)C8V*C20
UC48D 1.01
1.01
1.00
(F,L)C9(C,V)*C16
FC/MC/PC48C 1.01
1.01
0.99
(F,L)C9(C,V)*C16
FC/MC/PC48D 1.01
1.01
0.99
(F,L)C9(C,V)*C16
UC48D 1.01
1.01
0.99
(F,L)C9(C,V)*C20
FC/MC/PC48C 1.01
1.01
1.02
Continued on Page 18.