246786-CTG-B-0407

Unitary Products Group

5

For additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” document available online at www.upgnet.com
in the Product Catalog Section.

Thermostat Chart - AC

AC10

2 Stage Scroll A/C w/ Variable Speed Furnace - PV8/9; (F,L)*8/9V, (G,L)*8/9V, XYG8V-*, XYF8V-*, XYG9V-*, XYF9V-*

*DN22U00124

THERMOSTAT

Y

First Stage Cool

R

24-Volt Hot (Heat XFMR)

C

24-Volt Common

THERMOSTAT

Connection of the "C" 

Termainal, 24-Volt 

Common, is optional 

when used with batteries

*PP32U70124

Y

First Stage Cool

Y2

Second Stage Cool

R

24-Volt Hot (Heat XFMR)

C

24-Volt Common

W/W1

Single/First Stage Heat

W2

Second Stage Heat

G

Fan

Thermostat Installer 

Setup Number 0170 - 

System Type - must be 

set to 8 - 2 Heat/2 Cool 

Multistage Conventional

G

Fan

G

Fan

E/W1

First Stage Heat

W2

Second Stage Heat

*PP32U72124

RC

24-Volt Hot (Cool XFMR)

E/W1

First Stage Heat

L

Malfunction Light

W2

Second Stage Heat

G

Fan

E/W1

First Stage Heat

Y2

Second Stage Cool

C

24-Volt Common

Y1

First Stage Cool

*DP22U70124

HM

Humidistat

DHM

Dehumidistat

VARIABLE SPEED

FURNACE CONTROL

R

24-Volt Hot

CFM CONTROL

W2

Second Stage Heat

Y1

First Stage Cool

*PP32U71124

THERMOSTAT

24V HUMIDIFIER

(Optional)

(X/L)

Malfunction Light

(O)

Reversing Valve– Energized in Cool

TWO STAGE

AIR CONDITIONING

Comfort Alert

Interface

HUM

Dehumidification - Open on Humidity Rise

C

24-Volt Common

C

24-Volt Common

R

24-Volt Hot

W2

Second Stage Heat

G

Fan

Y2

Second Stage Cool

E/W1

First Stage Heat

RC

24-Volt Hot (Cool XFMR)

Y1

First Stage Cool

R

24-Volt Hot

Y/Y2

Single/Second Stage Cool

Y2

Second Stage Cool

Y

First Stage Cool

Y2

Second Stage Cool

W2

Second Stage Heat

G

Fan

R

24-Volt Hot

W

First Stage Heat

R

24-Volt Hot

*DN22C00124

THERMOSTAT

Y2

Second Stage Cool

Y1

First Stage Cool

C

24-Volt Common

C

24-Volt Common

THERMOSTAT

Thermostat Installer Setup 

Number 15 - Compressor 

Protection - must be set to 5

( ) CONVENIENCE TERMINAL

NO FUNCTION IN THIS APPLICATION.

E2/P Switch must be in 

the E2 position and the 

Humidistat Jumper on 

CFM Control must be 

in the 'YES' position 

for Dehumidification

Step 1 of Thermostat User 

Configuration Menu 

must be set to MS 2

Connection of the "C" 

Termainal, 24-Volt Common, 

is optional 

when used with batteries

Step 16 of Thermostat 

User Configuration Menu 

must be set to ON to use 

Comfort Alert Features

Thermostat Installer Setup 

Number 1 - System Type - 

must be set to 6 - 2 

Heat/2 Cool Conventional

Connection of the "C" Termainal, 

24-Volt

Common, is optional 

when used with batteries

Connection of the "C" 

Termainal, 24-Volt 

Common, is optional 

when used with batteries

Step 1 of Thermostat User 

Configuration Menu must be 

set to MLTI STG

Summary of Contents for Echelon FC9V

Page 1: ...wo stage inducer operation Provides increased comfort level very quiet unit opera tion Adjustable delay timer allows two stage operation with sin gle stage thermostat Compact easy to install ideal height 40 cabinet Blower off delay for cooling SEER improvement Easy to connect power control wiring Built in high level self diagnostics with fault code display Low unit amp requirement for easy replace...

Page 2: ...NSATE DRAIN OPENING 1 3 4 HORIZONTAL CONDENSATE DRAIN OPENING 1 3 4 JUNCTION BOX HOLE 7 8 GAS PIPE ENTRY 1 1 2 CONDENSATE DRAIN HOLE 7 8 29 22 3 4 21 1 4 18 1 2 9 1 8 8 1 2 30 1 8 23 11 16 E FRONT A 40 DIMENSIONS Models Nominal CFM Cabinet Size Cabinet Dimension A in B in C in D in E IN FC9V060B12DH11 1200 B 17 1 2 16 1 4 15 1 3 4 2 3 8 FC9V080B12DH11 1200 B 17 1 2 16 1 4 15 1 3 4 2 3 8 FC9V080C16...

Page 3: ...A 1287 772 D A 1337 802 C C 1132 668 D C HIGH LOW HEAT CFM WITHOUT FILTERS FC9V060B12DH11 FC9V080B12DH11 Jumper Settings High Low High Low HEAT Tap ADJ Tap 1137 720 1386 962 A Any 974 625 1322 892 B Any 883 593 1250 849 C Any 825 561 1159 768 D Any FC9V080C16DH11 FC9V100C20DH11 Jumper Settings High Low High Low HEAT Tap ADJ Tap 1732 1173 1912 1237 A Any 1631 1110 1688 1079 B Any 1493 1008 1545 967...

Page 4: ...return air openings or return air opening size and add to the ESP from Step 2 to determine the total system static If total system static matches a ESP value in the airflow table i e 0 20 0 60 etc the system airflow corresponds to the intersection of the ESP column and Model Blower Speed row FILTER SIZES Input Output BTU H CFM Cabinet Size Top Return Filter in 60 56 1200 B 2 14 x 20 80 75 1200 B 2...

Page 5: ... O Reversing Valve Energized in Cool TWO STAGE AIR CONDITIONING Comfort Alert Interface HUM Dehumidification Open on Humidity Rise C 24 Volt Common C 24 Volt Common R 24 Volt Hot W2 Second Stage Heat G Fan Y2 Second Stage Cool E W1 First Stage Heat RC 24 Volt Hot Cool XFMR Y1 First Stage Cool R 24 Volt Hot Y Y2 Single Second Stage Cool Y2 Second Stage Cool Y First Stage Cool Y2 Second Stage Cool W...

Page 6: ...elay on furnace to OFF HM Humidistat BSG Bonnet Sensor Bonnet Sensor Optional BS Bonnet Sensor AUX Auxiliary Heat E W1 First Stage Auxiliary Heat E W1 First Stage Auxiliary Heat W Auxiliary Heat Y2 Second Stage Heat Cool DHM Dehumidistat HUM Dehumidification Open on Humidity Rise Y2 Second Stage Heat Cool Y2 Second Stage Heat Cool Y2 Second Stage Heat Cool Y 2 O Reversing Valve Energized in Cool L...

Page 7: ... coils These kits are not required with MC FC series coils but please ensure that the coil and furnace are secured and that there are no air leaks CONDENSATE NEUTRALIZER KIT 1NK0301 Neutralizer cartidge has a 1 2 plastic tube fittings for installa tion in the drain line Calcium carbonate refill media is also avaiable from the Source 1 Parts p n 026 30228 000 HIGH ALTITUDE PRESSURE SWITCHES For ins...

Page 8: ...ange without notice Printed in U S A 246786 CTG B 0407 Copyright by York International Corp 2007 All rights reserved Supersedes 246786 036 21637 002 Rev A 1205 Unitary 5005 Norman Products York OK Group Drive 73069 ...

Reviews: