260614-CTG-C-0407

2

Unitary Products Group

Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.
* Wire size and overcurrent protection must comply with the National Electric Code.

NOTES: 

1. For altitudes above 2000 ft. reduce capacity 4% for each 1000 ft. above sea level.
2. Wire size based on copper conductors, 60°C, 3% voltage drop.
3. Continuous return air temperature must not be below 55°F.
4. All filters must be high velocity cleanable type.

 

13-7/8

7/8

23-3/4

7/8

30-1/8

1-1/2” GAS
PIPE ENTRY

7/8” JUNCTION
BOX HOLE

T-STAT WIRING
7/8” K.O.

CONDENSATE
DRAIN 7/8” K.O.

OPTIONAL RETURN AIR
CUT-OUT (either side)
FOR USE WITH
EXTERNAL FILTER
FRAME

LEFT SIDE

RIGHT SIDE

26-3/4

1-1/2

1-1/4

C

24-3/8

20

5/8

5/8

B

24-17/16

2

D

BOTTOM IMAGE

RETURN END

TOP IMAGE

SUPPLY END

1-1/2” GAS
PIPE ENTRY

7/8” JUNCTION
BOX HOLE

T-STAT WIRING
7/8” K.O.

CONDENSATE
DRAIN 7/8” K.O.

A

40

FRONT

CABINET AND DUCT DIMENSIONS

Models

Nominal

CFM

Cabinet

Size

Cabinet Dimension

A (in.)

B (in.)

C (in.)

D (in.)

FC9V040A12UP11

1200

A

14-1/2

13-1/2

11-1/2

6-1/4

FC9V060B12UP12

1200

B

17-1/2

16-1/4

14-1/2

8-1/2

FC9V080B12UP11

1200

B

17-1/2

16-1/4

14-1/2

8-1/2

FC9V080C16UP12

1600

C

21

19-3/4

18

8-7/8

FC9V100C20UP12

2000

C

21

19-3/4

18

8-7/8

FC9V120D20UP12

2000

D

24-1/2

23-1/4

21-1/2

10-5/8

ELECTRICAL AND PERFORMANCE DATA

Models

Input 

High/Low

Output 

High/Low

Nominal 

Airflow*

Cabinet 

Width

Total Unit

AFUE

High Fire 

Air Temp. Rise

Low Fire 

Air Temp. Rise

MBH

MBH

CFM

In.

Amps

%

°F

°F

FC9V040A12UP11

40/26

38/24

1200

14-1/2

9

94.0

35 - 65

35 - 65

FC9V060B12UP12

60/39

56/36

1200

17-1/2

9

95.0

40 - 70

20 - 50

FC9V080B12UP11

80/52

75/49

1200

17-1/2

9

92.5

45 - 75

45 - 75

FC9V080C16UP12

80/52

75/49

1600

21

12

95.0

45 - 75

20 - 50

FC9V100C20UP12

100/65

93/60

2000

21

14

95.0

45 - 75

20 - 50

FC9V120D20UP12

120/78

112/73

2000

24-1/2

14

95.0

40 - 70

20 - 50

Models

Input 

High/Low

Max. Outlet 

Air Temp.

Blower

Blower 

Size

Max. 

Over-

current 
Protect

Min. Wire Size

(awg) @ 75 ft. 

One Way

Operating 

Wgt.

MBH

°F

HP

Amps

In.

Lbs.

FC9V040A12UP11

40/26

165

1/2

7.7

11 x 8

20

14

121

FC9V060B12UP12

60/39

170

1/2

7.7

11 x 8

20

14

135

FC9V080B12UP11

80/52

175

1/2

7.7

11 x 8

20

14

142

FC9V080C16UP12

80/52

175

3/4

9.6

11 x 10

20

14

157

FC9V100C20UP12

100/65

175

1

12.8

11 x 11

20

12

164

FC9V120D20UP12

120/78

170

1

12.8

11 x 11

20

12

180

Summary of Contents for FC9V Series

Page 1: ...as valve Two stage inducer operation Variable speed ECM blower operation Provides increased comfort level very quiet unit opera tion Adjustable delay timer allows two stage operation with sin gle stage thermostat Compact easy to install ideal height 40 cabinet Blower off delay for cooling SEER improvement Easy to connect power control wiring Built in high level self diagnostics with fault code dis...

Page 2: ...NS Models Nominal CFM Cabinet Size Cabinet Dimension A in B in C in D in FC9V040A12UP11 1200 A 14 1 2 13 1 2 11 1 2 6 1 4 FC9V060B12UP12 1200 B 17 1 2 16 1 4 14 1 2 8 1 2 FC9V080B12UP11 1200 B 17 1 2 16 1 4 14 1 2 8 1 2 FC9V080C16UP12 1600 C 21 19 3 4 18 8 7 8 FC9V100C20UP12 2000 C 21 19 3 4 18 8 7 8 FC9V120D20UP12 2000 D 24 1 2 23 1 4 21 1 2 10 5 8 ELECTRICAL AND PERFORMANCE DATA Models Input Hig...

Page 3: ...0 920 C A 1250 790 1290 790 D A 1310 810 1360 840 C C 1090 690 1140 690 D C HIGH LOW HEAT CFM FC9V040A12UP11 FC9V060B12UP12 Jumper Settings High Low High Low HEAT Tap ADJ Tap 1045 740 1110 710 A Any 905 645 960 640 B Any 825 595 870 600 C Any 765 590 830 570 D Any FC9V080B12UP11 FC9V080C16UP12 Jumper Settings High Low High Low HEAT Tap ADJ Tap 1330 880 1490 990 A Any 1180 810 1350 900 B Any 1100 7...

Page 4: ...on the number of return air openings or return air opening size and add to the ESP from Step 3 to determine the total system static 5 If total system static matches a ESP value in the airflow table i e 0 20 0 60 etc the system airflow corre sponds to the intersection of the ESP column and Model Blower Speed row FILTER SIZES Input Output BTU H CFM Cabinet Size Side Return Filter in Bottom Return Fi...

Page 5: ... O Reversing Valve Energized in Cool TWO STAGE AIR CONDITIONING Comfort Alert Interface HUM Dehumidification Open on Humidity Rise C 24 Volt Common C 24 Volt Common R 24 Volt Hot W2 Second Stage Heat G Fan Y2 Second Stage Cool E W1 First Stage Heat RC 24 Volt Hot Cool XFMR Y1 First Stage Cool R 24 Volt Hot Y Y2 Single Second Stage Cool Y2 Second Stage Cool Y First Stage Cool Y2 Second Stage Cool W...

Page 6: ...elay on furnace to OFF HM Humidistat BSG Bonnet Sensor Bonnet Sensor Optional BS Bonnet Sensor AUX Auxiliary Heat E W1 First Stage Auxiliary Heat E W1 First Stage Auxiliary Heat W Auxiliary Heat Y2 Second Stage Heat Cool DHM Dehumidistat HUM Dehumidification Open on Humidity Rise Y2 Second Stage Heat Cool Y2 Second Stage Heat Cool Y2 Second Stage Heat Cool Y 2 O Reversing Valve Energized in Cool L...

Page 7: ...ts all cabinet sizes Attaches to side of furnace cabinet in side return applications Holds any 16x25x1 permanent or disposable filter SIDE RETURN FILTER RACK 1SR0302 All Models 1SR0200 All Models BOTTOM RETURN FILTER RACK 1BR0114 or 1BR0214 For 14 1 2 cabinets 1BR0117 or 1BR0217 For 17 1 2 cabinets 1BR0121 or 1BR0221 For 21 cabinets 1BR0124 or 1BR0224 For 24 1 2 cabinets HIGH ALTITUDE PRESSURE SWI...

Page 8: ...o change without notice Printed in U S A 260614 CTG C 0407 Copyright by York International Corp 2007 All rights reserved Supersedes 260614 CTG B 0806 Unitary 5005 Norman Products York OK Group Drive 73069 NOTES ...

Reviews: