background image

It is also acceptable to connect the selected motor speed with a
pig tail joined to both heating and cooling speed wires with a
wire nut. As a safety precaution against accidental disconnec-
tion of the wires by vibration, it is advisable to secure the wire
nut and wires with a few wraps of electricians tape.

CAUTION: Do not connect power leads between mo-
tor speeds. The neutral wire must always be con-
nected to the motor's designated neutral terminal.

WARNING: Disconnect the power supply to the fur-
nace before opening the blower access door to serv-
ice the air filter, fan or motor. Failure to shut off power
could allow the blower to start unexpectedly, creating
a risk of death or personal injury.

If the joining of the blower speed wiring is done in the furnace
junction box, tape off both ends of the unused wire.

Do not use the blower speed wires as a source of power to
accessories as electronic air cleaners and humidifier
transformers unless it is certain that only one motor speed
will be used
. The unused motor taps auto--generate suffi-
ciently high voltages to damage accessory equipment.

MAINTENANCE AND SERVICE

Routine Maintenance By Home Owner

Other than remembering to arrange for the annual professional
servicing of the furnace by the service or installation contractor,
the most important routine service performed by the home
owner is to maintain the air filter or filters. A dirty filter can cause
the furnace to over--heat, fail to maintain indoor temperature
during cold weather, increase fuel consumption and cause
component failure.

The furnace filter(s) should be inspected, cleaned or replaced
monthly. The furnace is factory equipped with a semi--
permanent type filter. If the filter is damaged, replace with filters
of the same size and type. (See Page 5 for listing).

During the routine service, inspect the general condition of the
furnace watching for signs of oil leaks in the vicinity of the oil
burner, soot forming on any external part of the furnace, soot
forming around the joints in the vent pipe, etc. If any of these
conditions are present, please advice your service or installa-
tion contractor.

Annual Service By Contractor

CAUTION: The combustion chamber (firepot) is frag-
ile. Use care when inspecting and cleaning this area.

The heat exchanger should be inspected periodically and
cleaned if necessary. if cleaning is necessary, SHUT OFF
POWER TO THE FURNACE 
and remove the burner. Using a
stiff brush with a wire handle, brush off scale and soot from in-
side the drum and flue pipe. To clean the radiator, remove the
round covers on the inner front panel to gain access to the
cleaning ports.

When this procedure is done for the first time, carefully cut
away the insulation covering the opening with a sharp knife.
Loosen the nuts on the radiator clean--outs. DO NOT RE-
MOVE THE NUTS. Remove the covers carefully to avoid tear-
ing the gaskets. A wire brush can be used to loosen dirt and
debris on the inside surfaces of the radiator.

Clean out all accumulated dirt, soot and debris with a wire han-
dled brush and an industrial vacuum cleaner. Before replacing
the clean--out covers, inspect the gaskets. If the gaskets are
broken, remove the remnants and replace with new gaskets.
Snug the cleanout covers. DO NOT OVER--TORQUE THE

CLEAN--OUT NUTS. Replace the inner front panel clean--out
covers.

NOTE: A radiator clean--out assembly inadvertently
dropped into the interior of the furnace can usually be
easily retrieved with a magnet on a wire handle or
stout string.

The direct drive blower motor is factory oiled. Under normal op-
erating conditions it does not require oiling for the first two
years. Oil sparingly (a few drops) in each oil port with SAE 20
non--detergent oil. Oiling is most easily done with a “tele--
spout” oilier. This oiler has a long flexible plastic spout. DO
NOT OVER--LUBRICATE. Excess oil causes premature elec-
tric motor failure.

Inspect the blower fan. Clean if necessary.

Oil Burner Maintenance: Follow the instructions of the oil
burner manufacturer. (See oil burner manufacturer's instruc-
tions supplied with furnace). It is advisable to change the oil
burner nozzle and oil filter on an annual basis.

The venting system should be cleaned and inspected for signs
of deterioration. Replace pitted or perforated vent pipe and fit-
tings. The barometric damper should open and close freely.

All electrical connections should be checked to ensure tight
connections. Safety controls such as the high limit controls
should be tested for functionality. The fan control should be
checked to ensure that the “fan off” function continues to stop
the blower fan at temperatures between 90

°

F to 100

°

F.

OPERATING INSTRUCTIONS

Before Lighting

1. Open all supply and return air registers and grilles.

2. Open all valves in oil pipes.

3. Turn on electric power supply

To Light Unit

1. Set the thermostat above room temperature to call for

heat. The burner should start. NOTE: It may be necessary
to press the RESET button on the primary combustion
control relay.

2. After a short period of time, as the furnace becomes warm

enough the act upon the fan control (L6064A), or preheats
the bi--metallic element (L4064W), the blower should
start.

3. Set the thermostat below room temperature. The oil

burner should stop.

4. The air circulation blower will continue to run as long as the

temperature in the furnace is higher than the “FAN OFF”
setting on the fan control. Typical “fan on” values range
from 120° F to 130° F. Typical “fan off” temperatures range
between 90° F and 100° F. The fan control adjustments
may be altered if the air at the room registers is uncom-
fortably high upon blower start up or shutdown, the fan
control settings can be lowered.

5. The adjustments to the fan control settings should be

made by measuring the temperature of the air in the sup-
ply air take--off, or within the first few inches of the supply
air trunk. The side mid point of the transition is usually
ideal, providing that the thermometer probe is beyond the
“line of sight” wherein false readings from radiant heat
could be observed. The system temperature rise, the dif-
ference in temperature between the supply air and return
air, will typically range between 65° F and 70° F.

Unitary Products Group

9

035-14289-000 Rev. A (0701)

Summary of Contents for P*DHX12F0801

Page 1: ...ency or the oil supplier P HB UPFLOW INSTALLATION INSTRUCTION OIL FIRED WARM AIR FURNACES Supersedes 035 14289 000 A 300 035 14289 000 A 1101 CAUTION THIS PRODUCT MUST BE INSTALLED IN STRICT COM PLIANCE WITH THE ENCLOSED INSTALLATION IN STRUCTIONS AND ANY APPLICABLE LOCAL STATE AND NATIONAL CODES INCLUDING BUT NOT LIM ITED TO BUILDING ELECTRICAL AND ME CHANICAL CODES WARNING IMPROPER INSTALLATION ...

Page 2: ...ns provided the results obtained are in substantial agreement with and not less than those obtained using the procedure described in the manual LOCATION OF UNIT The furnace should be located such that the flue connection to the chimney is short direct and consists of as few elbows as possible When possible the unit should be centralized with re spect to the supply and return air duct work A centra...

Page 3: ...6F12001 are factory shipped for downflow installation Downflow If the furnace is to be installed in a downflow application a com bustible floor base must be used either 1CB0312 or 1CB0316 Refer to Figure 1 Horizontal For applying the furnace in a horizontal left or horizontal right application follow these steps 1 Rotate the furnace 90 degrees to the desired position 2 Remove three nuts and washer...

Page 4: ...SUPPLY AIR RETURN AIR P DHX12F08001 51 22 31 1 4 19 19 18 18 5 P DHX16F12001 62 22 1 4 22 1 4 20 1 2 20 1 2 18 18 6 LOWBOY SUPPLY AIR RETURN AIR P LBX12F08001 31 22 43 20 1 2 18 5 8 20 1 2 18 5 8 5 REAR P LBX16F12001 41 22 52 1 2 20 1 2 18 5 8 20 1 2 18 5 8 6 REAR P LBX16F14501 41 22 52 1 2 20 1 2 18 5 8 20 1 2 18 5 8 6 REAR P LBX20F19001 56 26 49 24 22 24 22 7 REAR TABLE 2 UNIT DIMENSIONS C E K H...

Page 5: ... 2 1 2 3 1200 P DHX16F12001 140 120 1 0 80 1 1593 12 0 15 14 11 x 10 1 2 1 20 x 20 3 3 1 2 4 1600 LOWBOY P LBX12F08001 91 80 65 85 1 1717 12 0 15 14 12 x 9 1 2 1 20 x 20 2 2 1 2 3 3 1 2 4 1200 P LBX16F12001 140 120 1 0 83 4 1585 12 0 15 14 12 x12 1 2 1 20 x 25 3 3 1 2 4 1600 P LBX16F14501 168 145 1 20 83 5 1585 12 0 15 14 12 x 12 1 2 1 20 x 25 3 3 1 2 4 1600 P LBX20F19001 231 190 1 65 78 0 2135 12...

Page 6: ...emperature sensitive fan switch is actuated by a helical bi metal sensing element enclosed in a metal guard and controls the circulating air blower This provides a delay between the burner ignition and blower start up to eliminate ex cessive flow of cold air when the blower comes on Blower shutdown is also delayed to remove any residual heat from the heat exchanger and improve the annual efficienc...

Page 7: ...e lift on a single line system is 8 ft Lift should be measured from the bottom outlet of the tank to the inlet of the burner Sizing a single line system is complex because of the difficulty estimating the pressure drop through each fitting bend and component in the line In general keep single line systems short as possible If the furnace is to be installed in a sus pended position a two pipe syste...

Page 8: ... amping of the direct drive blower motor Selecting a lower blower speed may cor rect this problem Direct drive blower speeds are adjusted by changing the hot wires to the motor winding connections Please refer to wiring diagram on Page 12 or the wiring diagram label affixed to the furnace THE NEUTRAL WIRE normally the white wire IS NEVER MOVED TO ADJUST THE BLOWER SPEED It is possible and acceptab...

Page 9: ...nd debris with a wire han dled brush and an industrial vacuum cleaner Before replacing the clean out covers inspect the gaskets If the gaskets are broken remove the remnants and replace with new gaskets Snug the cleanout covers DO NOT OVER TORQUE THE CLEAN OUT NUTS Replace the inner front panel clean out covers NOTE A radiator clean out assembly inadvertently dropped into the interior of the furna...

Page 10: ...URNER SET UP The burner air supply is adjusted to maintain the fuel to air ratio to obtain ideal combustion conditions Alack of air causes soft and sooty flames resulting in soot build up throughout the heat exchanger passages Excess combustion air causes a bright roaring fire and high stack temperatures resulting in poor fuel efficiency Preparations Drill a 1 4 test port in the venting ideally at...

Page 11: ...e flue gases are above the range the blower may require speeding up Stack temperature varies directly with the system temperature rise System temperature rise is the difference between the furnace outlet temperature and the furnace inlet temperature as measured in the vicinity of the connection between the plenum take offs and the trunk ducts Typical temperature rise values range between 65 F and ...

Page 12: ...H 1752 1691 1659 1593 1525 MED HIGH 1454 1454 1417 1379 1300 MED LOW 975 944 912 879 844 LOW 631 593 552 515 486 P LBX12F08001 HIGH 1917 1885 1820 1717 1608 MED HIGH 1590 1608 1590 1532 1430 MED LOW 1096 1096 1096 1068 1039 LOW 696 647 692 647 598 P LBX16F12001 P LBX16F14501 HIGH 1810 1740 1675 1585 1480 MED HIGH 1570 1540 1495 1445 1348 MED LOW 1090 1080 1070 1065 1036 LOW 710 700 690 665 614 P L...

Page 13: ...Unitary Products Group 13 035 14289 000 Rev A 0701 WIRING DIAGRAM ALL MODELS ...

Page 14: ...f necessary Ensure that erratic pressure readings are not caused by defective fuel oil lines Air getting into fuel oil lines or fuel oil line dirty clogged or in some manner defective Check oil lines Replace any compression fittings found with high quality flared fittings Check for any signs of oil leaks An oil leak is a potential source of air or contaminants Defective burner motor Check burner m...

Page 15: ...ure Adjust the oil burner combustion air band and draft regulator to gain the highest CO2 possible with a Bacharach No 1 smoke Heat exchanger partially clogged Check for soot build up in heat exchanger flue passages especially in the outer radiator Furnace will not warm home to desired tempera ture Air flow blocked by dirty air filter Clean or replace air filter Thermostat adjustments or location ...

Page 16: ...nge without notice Printed in U S A Copyright by Unitary Products Group 1999 All rights reserved 035 14289 000 A 1101 Code EBY L F Supersedes 035 14289 A 000 300 5005 York Drive Norman OK 73069 Unitary Products Group ...

Reviews: