background image

 

21 

Table C-3:  System and General Troubleshooting 

continued

 

Problem Possible 

Cause 

Remedy 

System temperature rise too 
high. 

System temperature rise ideally should not exceed 85°F. Check 
for clogged air filters. Check blower fan for excess dirt build-up or 
debris. Speed up blower fan if necessary. 

Poor “fan off” delay timing 
selection, (fan stops too soon). 

Check “fan off” delay timing setting. Use a duct thermometer in the 
supply air plenum take-off or first few inches of the supply air trunk 
duct. Ideally, the fan will shut off at a temperature of 90° - 100°F. 
Manipulate the dip switch settings to come as close as possible to 
this “fan off” temperature. 

Fuel oil leak. 

Check fuel oil line for leaks. Repair or replace if necessary. 

Stack temperature too high. 

Check stack temperature. Stack temperatures will normally range 
from 350° to 450°F. Check draft regulator. Draft should be set to 
0.02 in. W.C. 

Excessive fuel oil 
consumption. 

Thermostat improperly adjusted 
or in poor location. 

Check thermostat heat anticipator setting against measured 
amperage draw.  Increase heat anticipator setting if necessary. If 
the thermostat is being influenced by drafts, sunlight, duct work, 
etc., relocate to more suitable location. 

Insufficient combustion air 
adjustment at oil burner, or 
improper draft pressure. 

Adjust the oil burner combustion air band and draft regulator to 
gain the highest practical CO

2

 or lowest practical O

2

 content in the 

flue gases. See Burner Set Up. 

Too much smoke. 

Heat exchanger partially 
clogged. 

Check for soot build-up in heat exchanger flue passages, 
especially in the outer radiator. 

Poor alignment between oil 
burner blast tube and fire pot. 

Check alignment. air tube should be centered with fire pot burner 
opening. Oil burner head should be ¼ inch back from the inside 
surface of the fire pot. 

Flame impingement caused by 
Incorrect nozzle angle. 

Check nozzle size and angle. (See Appendix A). Check distance 
from head to inside surface of the fire pot. 

Soot building up on 
blast tube (end 
coning). 

Defective fire-pot 

Check fire-pot. Repair or replace. 

Airflow blocked or dirty air filter. 

Clean or replace air filter. 

Thermostat adjustments or 
location. 

Check thermostat heat anticipator setting against measured 
amperage draw.  Increase heat anticipator setting if necessary. If 
the thermostat is being influenced by drafts, sunlight, duct work, 
etc., relocate to more suitable location. 

Insufficient airflow. 

Check all dampers. Open closed dampers including registers in 
unused rooms. Check system temperature rise. If temperature rise 
is too high, speed up blower fan. 

Defective high limit control. 

Test high limit function of all limit switches. Use a duct 
thermometer to assess accuracy of limit control. Check for 
obstructions to airflow around limit switch bi-metal elements. 
Replace control if necessary. 

Under-sized nozzle. 

Check nozzle. If problem is not caused by air flow problems, use 
larger nozzle, if permitted by rating plate. 

Blower fan motor stopping 
intermittently on overload. 

Check blower fan motor amperage draw. Check motor ventilation 
ports, clean if necessary. Replace motor if necessary. 

Furnace will not warm 
home to desired 
temperature. 

Burner motor stopping 
intermittently on overload. 

Check burner motor. Replace if necessary. 

Home does not heat 
evenly 

Improper distribution of heat. 

This is not likely to be a furnace problem. Balance duct system. 

Continues on next page

 

Summary of Contents for P*LBX16F14501

Page 1: ...ER SET UP 11 TABLE A 3 BELT DRIVE BLOWER SET UP 11 TABLE A 4 DIRECT DRIVE BLOWER CHARACTERISTICS 12 TABLE A 5 BELT DRIVE BLOWER CHARACTERISTICS 12 WIRING DIAGRAM MODEL P LBX16F14501 13 WIRING DIAGRAM...

Page 2: ...f the furnace and related equipment shall be installed in accordance with the regulations of CAN CSA B139 Installation Code For Oil Burning Equipment as well as in accordance with local codes When ins...

Page 3: ...tility room two 2 ventilation openings must be provided connecting to a well ventilated space full basement living room or other room opening thereto but not a bedroom or bathroom One opening shall be...

Page 4: ...CE The flue pipe must not be routed through concealed space because it must be visually checked for signs of deterioration during the annual inspection and servicing The flue pipe must not pass throug...

Page 5: ...Must be handled by competent masonry contractor G Collection of soot at narrow space in flue opening Lower light on extension cord Clean out with weighted brush or bag of loose gravel on end of line H...

Page 6: ...s greater than 10 PSIG may cause damage to the shaft seal If the height of the oil stored in a tank above the oil burner exceeds 11 feet it may be necessary to use a pressure regulating device approve...

Page 7: ...ts are closed System switch must be on HEAT if so equipped 4 Re connect the thermostat wire If the thermostat is serving a combination heating and air conditioning system pay particular attention to p...

Page 8: ...auses soft and sooty flames resulting in soot build up throughout the heat exchanger passages Excess combustion air causes a bright roaring fire and high stack temperatures resulting in poor fuel effi...

Page 9: ...at exchanger If the plenum take off is unsuitable the supply air temperature may be measured within the first 18 inches of the first segment of supply air trunk duct If the temperature rise is outside...

Page 10: ...a long flexible plastic spout DO NOT OVER LUBRICATE Excess oil may result in premature electric motor failure Inspect the blower fan Clean it if necessary Oil Burner Maintenance Follow the instruction...

Page 11: ...up the chimney between burner cycles NOTE THE USE OF THIS CONTROL CAN OCCASIONALLY CAUSE POST COMBUSTION NOZZLE DRIP TABLE A 2 DIRECT DRIVE BLOWER SET UP BLOWER SET UP COOLING CAPACITY 0 20 in w c 0 5...

Page 12: ...5 BELT DRIVE BLOWER CHARACTERISTICS CFM External Static Pressure Inches water column Furnace Model Motor HP Motor FLA T Blower Blower Pulley Motor Pulley Turns Out 0 20 0 30 0 40 0 50 0 60 0 2274 2080...

Page 13: ...13 WIRING DIAGRAM MODEL P LBX16F14501 WIRING DIAGRAM MODEL P LBX20F19001...

Page 14: ...to spark for 10 sec a Provides continuous spark after flame is sensed to assure that burner remains lit b Turns on LED diagnostic light c Starts carryover timer i Flame and call for heat are monitore...

Page 15: ...rner Motor Solenoid Valve LED Diagnostic Light RETURNS TO IDLE STATE FLAME FLAME FLAME FLAME NO FLAME NO FLAME FLAME LOST FLAME LOST REMAINS IN IDLE STATE R7184 SEQUENCE of OPERATION LOCKOUT STATE R71...

Page 16: ...NG IMPORTANT Due to the potential hazard of line voltage only a trained experienced service technician should perform the troubleshooting procedure PRELIMINARY STEPS Check the diagnostic light for ind...

Page 17: ...ntrol If the indicator light turns off replace cad cell bracket assembly Burner starts Trouble is in thermostat circuit Check thermostat wiring connections If connections are clean and tight check the...

Page 18: ...6 Reset oil primary control by pushing in and releasing red reset button Indicator light continues to flash at 1 Hz rate Verify that the control is not in restricted mode See notes at end of this tabl...

Page 19: ...h time a call for heat is successfully completed To reset from RESTRICTED MODE press and hold the reset button for 30 seconds When the LED flashes twice the device has reset NOTE Disable function Pres...

Page 20: ...sence of light Ensure that room light is not leaking into the cad cell compartment see diagnostic light section or manually measure cad cell resistance No fuel oil Check fuel oil supply Check that all...

Page 21: ...Poor alignment between oil burner blast tube and fire pot Check alignment air tube should be centered with fire pot burner opening Oil burner head should be inch back from the inside surface of the f...

Page 22: ...erature rise Slow down blower fan if necessary Supply air temperature too cool Excessive duct losses Check supply air ductwork Seal leaky joints and seams Insulate ductwork if necessary Fan control fa...

Page 23: ...with a pair of awls or similar tool 5 Begin fastening the flue pipe flanges together from inside the blower section to the furnace section with the six 1 4 20 x 3 4 inch screws saved from the removal...

Page 24: ...t 21A Cleanout Gasket 2 per unit 22 Filter Air 20 x 20 x1 Permanent 23 Box Junction 24 Wire Harness Blower Direct Drive 25 Wire Harness Fan and LImit ITEM DESCRIPTION 26 Centre Fan 26A Relay Replaceme...

Page 25: ...ner Channel Wire 20 Access Panel Blower Door 20A Handle Door 21 Baffle Front Panel 22 Baffle Top Front Panel 23 Burner Assembly Oil 23A Motor Burner ITEM DESCRIPTION 23B Pump Oil 23C Ignitor Solid Sta...

Page 26: ...nt and or representative that can assist you Visit our website at www source1parts com for the following information 1 Search for a part or browse the catalog 2 Find a dealer or distributor 3 Customer...

Page 27: ...27 NOTES...

Page 28: ...ct to change without notice Printed in U S A 280200 UIM A 1206 Copyright by Unitary Products Group 2006 All rights reserved Supersedes 035 14289 001 Rev B 0605 Unitary 5005 Norman Products York OK Gro...

Reviews: