background image

OIL BURNER 

P*LBX furnaces are equipped with 
Beckett AF Series oil burners with the 
Beckett CleanCut pump and R7184B oil 
primary control. The oil burner must align 
properly with combustion chamber 
(firepot). The combustion chamber is 
initially quite soft, but hardens and 
becomes quite brittle after the first firing. 
The firepot is held in place by a retaining 
bracket; however, it is possible for the 
firepot to shift if subjected to rough 
handling during transit. 

 

BEFORE OPERATING THE 
FURNACE CHECK BURNER 
ALIGNMENT WITH COMBUSTION 
CHAMBER. THE END CONE OF THE 
AIR TUBE MUST BE CENTRED TO 
THE ACCOMODATING RING 
PROVIDED IN THE DESIGN OF THE 
COMBUSTION CHAMBER. ADJUST 
ALIGNMENT AS NECESSARY 
BEFORE THE FIRST FIRING. 

OIL BURNER NOZZLES 

All furnace models are certified for 
multiple firing rates. Choose the firing 
rate that most closely matches the 
calculated heat loss of the building. 
Models, firing rates and nozzles are 
listed in Table A-1. 

BURNER ELECTRODES 

Correct positioning of the electrode tips 
with respect to each other, to the fuel oil 
nozzle, and to the rest of the burners is 
essential for smooth light ups and proper 
operation. The electrode tips should be 

adjusted to a gap of 5/32”, 1/16” ahead 
of the nozzle, 5/16” above the centerline 
of the nozzle. The “Z” dimension (front 
edge of the burner head to the front face 
of the nozzle is 1-1/8 inches. 

Electrode positioning should be checked 
before the first firing of the furnace. 

The electrode porcelains should be free 
of cracks, the electrode tips should be 
tapered and free of burrs, and the 
contact rods must be clean and be in 
firm contact with the ignition transformer 
contact springs. The electrodes must not 
come into contact with the burner head. 

OIL BURNER SET-UP 

The burner air supply is adjusted to 
maintain the fuel to air  ratio to obtain 
ideal combustion conditions. A lack of air 
causes "soft" and "sooty" flames, 
resulting in soot build-up throughout the 
heat exchanger passages. Excess 
combustion air causes a bright roaring 
fire and high stack temperatures 
resulting in poor fuel efficiency.  

PREPARATIONS: 

Drill a 1/4” test port in the venting, ideally 
at least 2 flue pipe diameters away from 
the furnace breeching, if venting 
horizontally from the furnace, (typically 
P*LBX) or from the flue pipe elbow if 
venting vertically before reaching the 
furnace. (see Figures 4 and 5). 

The test port will allow flue gas samples 
to be taken and stack temperatures to be 
measured. 

Before starting the burner, check the 
burner alignment with the combustion 
chamber (fire pot), check that the correct 

nozzle is tightened into place, and that 
the burner electrodes are properly 
positioned. 

The Beckett burner bulk air band should 
be closed, and the air shutter initial 
setting should be approximately 7.00. 

Note A: Locate hole at least 6 inches on 
the furnace side of the draft control. 

Note B: Ideally, hole should be at least 
12 inches from breeching or elbow. 

PROCEDURE: 

Start the burner and allow it to run at 
least ten minutes. Set the air shutter to 
give a good flame visually. The 
combustion air supply to the burner is 
controlled by adjusting the air shutter on 
the left side of the burner, and, if 
necessary, the bulk air band. To adjust, 
loosen the bolt on the movable shutter. 
Move the shutter gradually until a good 
flame (visually) has been achieved. Re-
snug the bolt. 

Check the initial draft setting as the 
furnace warms up. The draft may be 
measured at the test port. The final 
breech draft should be  - 0.02 inches 
W.C. to provide adequate over-fire draft. 

Check the oil pump pressure. Standard 
operating pressure is 100 PSIG. 

After reaching steady state, take a 
smoke test. If not indicating a trace, set 
the combustion air controls to provide a 
trace. 

Typically, the CO

2

 reading will range 

from 11.5% to 13.5%. 

After the air adjustments have been 
completed, and the air shutter or air 

Fig. 4: Horizontal Smoke Test Port Location 

Fig. 5: Vertical Smoke Test Port Location 

Summary of Contents for P*LBX16F14501

Page 1: ...ER SET UP 11 TABLE A 3 BELT DRIVE BLOWER SET UP 11 TABLE A 4 DIRECT DRIVE BLOWER CHARACTERISTICS 12 TABLE A 5 BELT DRIVE BLOWER CHARACTERISTICS 12 WIRING DIAGRAM MODEL P LBX16F14501 13 WIRING DIAGRAM...

Page 2: ...f the furnace and related equipment shall be installed in accordance with the regulations of CAN CSA B139 Installation Code For Oil Burning Equipment as well as in accordance with local codes When ins...

Page 3: ...tility room two 2 ventilation openings must be provided connecting to a well ventilated space full basement living room or other room opening thereto but not a bedroom or bathroom One opening shall be...

Page 4: ...CE The flue pipe must not be routed through concealed space because it must be visually checked for signs of deterioration during the annual inspection and servicing The flue pipe must not pass throug...

Page 5: ...Must be handled by competent masonry contractor G Collection of soot at narrow space in flue opening Lower light on extension cord Clean out with weighted brush or bag of loose gravel on end of line H...

Page 6: ...s greater than 10 PSIG may cause damage to the shaft seal If the height of the oil stored in a tank above the oil burner exceeds 11 feet it may be necessary to use a pressure regulating device approve...

Page 7: ...ts are closed System switch must be on HEAT if so equipped 4 Re connect the thermostat wire If the thermostat is serving a combination heating and air conditioning system pay particular attention to p...

Page 8: ...auses soft and sooty flames resulting in soot build up throughout the heat exchanger passages Excess combustion air causes a bright roaring fire and high stack temperatures resulting in poor fuel effi...

Page 9: ...at exchanger If the plenum take off is unsuitable the supply air temperature may be measured within the first 18 inches of the first segment of supply air trunk duct If the temperature rise is outside...

Page 10: ...a long flexible plastic spout DO NOT OVER LUBRICATE Excess oil may result in premature electric motor failure Inspect the blower fan Clean it if necessary Oil Burner Maintenance Follow the instruction...

Page 11: ...up the chimney between burner cycles NOTE THE USE OF THIS CONTROL CAN OCCASIONALLY CAUSE POST COMBUSTION NOZZLE DRIP TABLE A 2 DIRECT DRIVE BLOWER SET UP BLOWER SET UP COOLING CAPACITY 0 20 in w c 0 5...

Page 12: ...5 BELT DRIVE BLOWER CHARACTERISTICS CFM External Static Pressure Inches water column Furnace Model Motor HP Motor FLA T Blower Blower Pulley Motor Pulley Turns Out 0 20 0 30 0 40 0 50 0 60 0 2274 2080...

Page 13: ...13 WIRING DIAGRAM MODEL P LBX16F14501 WIRING DIAGRAM MODEL P LBX20F19001...

Page 14: ...to spark for 10 sec a Provides continuous spark after flame is sensed to assure that burner remains lit b Turns on LED diagnostic light c Starts carryover timer i Flame and call for heat are monitore...

Page 15: ...rner Motor Solenoid Valve LED Diagnostic Light RETURNS TO IDLE STATE FLAME FLAME FLAME FLAME NO FLAME NO FLAME FLAME LOST FLAME LOST REMAINS IN IDLE STATE R7184 SEQUENCE of OPERATION LOCKOUT STATE R71...

Page 16: ...NG IMPORTANT Due to the potential hazard of line voltage only a trained experienced service technician should perform the troubleshooting procedure PRELIMINARY STEPS Check the diagnostic light for ind...

Page 17: ...ntrol If the indicator light turns off replace cad cell bracket assembly Burner starts Trouble is in thermostat circuit Check thermostat wiring connections If connections are clean and tight check the...

Page 18: ...6 Reset oil primary control by pushing in and releasing red reset button Indicator light continues to flash at 1 Hz rate Verify that the control is not in restricted mode See notes at end of this tabl...

Page 19: ...h time a call for heat is successfully completed To reset from RESTRICTED MODE press and hold the reset button for 30 seconds When the LED flashes twice the device has reset NOTE Disable function Pres...

Page 20: ...sence of light Ensure that room light is not leaking into the cad cell compartment see diagnostic light section or manually measure cad cell resistance No fuel oil Check fuel oil supply Check that all...

Page 21: ...Poor alignment between oil burner blast tube and fire pot Check alignment air tube should be centered with fire pot burner opening Oil burner head should be inch back from the inside surface of the f...

Page 22: ...erature rise Slow down blower fan if necessary Supply air temperature too cool Excessive duct losses Check supply air ductwork Seal leaky joints and seams Insulate ductwork if necessary Fan control fa...

Page 23: ...with a pair of awls or similar tool 5 Begin fastening the flue pipe flanges together from inside the blower section to the furnace section with the six 1 4 20 x 3 4 inch screws saved from the removal...

Page 24: ...t 21A Cleanout Gasket 2 per unit 22 Filter Air 20 x 20 x1 Permanent 23 Box Junction 24 Wire Harness Blower Direct Drive 25 Wire Harness Fan and LImit ITEM DESCRIPTION 26 Centre Fan 26A Relay Replaceme...

Page 25: ...ner Channel Wire 20 Access Panel Blower Door 20A Handle Door 21 Baffle Front Panel 22 Baffle Top Front Panel 23 Burner Assembly Oil 23A Motor Burner ITEM DESCRIPTION 23B Pump Oil 23C Ignitor Solid Sta...

Page 26: ...nt and or representative that can assist you Visit our website at www source1parts com for the following information 1 Search for a part or browse the catalog 2 Find a dealer or distributor 3 Customer...

Page 27: ...27 NOTES...

Page 28: ...ct to change without notice Printed in U S A 280200 UIM A 1206 Copyright by Unitary Products Group 2006 All rights reserved Supersedes 035 14289 001 Rev B 0605 Unitary 5005 Norman Products York OK Gro...

Reviews: