LWLCWH COLUMBIA BOILER COMPANY REV. 13106
13
REQUIRED INPUT - CUBIC FEET OF GAS PER HOUR
L-18
L-20
L-22
L-24
L-30
L-32
CWH-170
CWH-240
CWH-300
CWH-390
CWH-475
CWH-610
NATURAL
168
252
336
420
560
700
PROPANE
67
101
134
168
224
280
WL-60
WL-90
WL-120
WL-140
WL-180
CWH-780
CWH-1200
CWH-1510
CWH-1810
CWH-2460
ROD LENGTH
840
1260
1680
1960
2520
PROPANE
336
504
672
784
1008
CAPACITY OF PIPE - CUBIC FEET OF GAS PER HOUR AT 0.2" W.C. PRESSURE DROP
Equivalent
1"
1-1/4"
1-1/2"
2"
2-1/2"
3"
4"
Length (ft)
10
425
725
1170
2360
4300
6250
12800
20
300
520
800
1700
3000
4500
9300
30
250
425
690
1400
2500
3750
7500
40
210
360
560
1200
2100
3200
6400
50
190
325
500
1100
1900
2850
5800
60
180
300
480
1000
1800
2300
4800
80
150
260
410
850
1550
2000
4200
100
135
230
370
750
1375
1680
3500
150
110
190
300
600
1100
1200
2750
200
75
165
260
540
950
1000
2000
Fitting
Equivalent Lengths of Standard Pipe in Feet for Listed Fittings
Std. Tee
5.5
7.5
9.0
12.0
13.5
15
20
Std. Elbow
2.7
3.7
4.5
5.5
6.1
8
11
Vent lines, if required, are to be run outside the building, stopping clear of windows or fresh air intakes.
The vent should terminate in a way that will not allow the possibility of water, dirt, insects, animals,
and other matter from entering and clogging the vent pipe.
GAS TYPE
GAS TYPE
Summary of Contents for CWH series
Page 2: ......
Page 34: ...LWLCWH COLUMBIA BOILER COMPANY REV 3107 31 ...
Page 35: ...LWLCWH COLUMBIA BOILER COMPANY REV 3107 32 SPECIFICATIONS AND DATA ...
Page 36: ...LWLCWH COLUMBIA BOILER COMPANY REV 3107 33 ...
Page 37: ...LWLCWH COLUMBIA BOILER COMPANY REV 3107 34 ...
Page 38: ...LWLCWH COLUMBIA BOILER COMPANY REV 3107 35 ...
Page 39: ...LWLCWH COLUMBIA BOILER COMPANY REV 3107 36 SPECIFICATIONS AND DATA 14 2 ...
Page 45: ...42 ...
Page 46: ...43 ...
Page 47: ...44 ...
Page 48: ...45 ...
Page 49: ...LWLCWH COLUMBIA BOILER COMPANY REV 3107 46 ...
Page 50: ...LWLCWH COLUMBIA BOILER COMPANY REV 3107 47 ...
Page 51: ...48 ...
Page 52: ...49 ...
Page 53: ...50 ...
Page 54: ......
Page 55: ......