InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
102
7.6.8
Peak shaving based on Active and Apparent Power
The Peak shaving function is active only in AUT mode in parallel to Mains operation. Peak shaving is
based on Object P or Apparent power consumption (consumption of load). If load consumption
increases over
ProcessControl:
PeakLevelStart
or
ProcessControl:
PeakKVAStart
for period longer
than
ProcessControl:
PeakAutS/S
or
ProcessControl:
PeakKVAS/S del
the gen-set group is started
(BO
Sys
start/stop
is
activated).
If
load
consumption
decreases
below
ProcessControl:
PeakLevelStop
or
ProcessControl:
PeakKVAStop
for
period
longer
than
ProcessControl:
PeakAutS/S del
or
ProcessControl:
PeakKVAS/S del
the gen-set group is stopped.
Both Peak shaving based on kW and kVA can work simultaneously (S
YS START
/
STOP
is activated if at
least one condition is fulfilled).
PeakLevelStart
PeakAutS/S del
A
c
tu
a
l
p
o
w
e
r
[
k
W
]
Time
PeakLevelStop
PeakAutS/S del
Sys start/stop
Figure:
Example of peak shaving function based on Active power (the same function for Apparent power)
N
OTE
:
Function Peak Shaving based on Apparent power is not available for IM-NT-GC controller.
7.7
Remote Alarm Messaging
It is possible to use up to five channels for Active Call, Email and SMS upon defined type of Alarm. It
is possible to define protection type for all ENABLED channels to react. All the possibilities in
InteliMains are: History record, Alarm only, Warning, Mains protect and Mains protect with Reset. Find
more information about alarm types in the chapter Protections and alarm management.
7.7.1
Communication Types for Remote Alarm Messaging
Below there all types of communication available for each Active Call channel.
DATA-ANA
: This option sends a complete archive to the recipient's PC via analog modem. An analog
modem must be connected either to one of controller COM ports or to one of I-LB modules connected
to the controller via CAN2 bus. The channel address must contain complete telephone number of the
recipient's PC where InteliMonitor is running in Active call receiving mode.
DATA-GSM:
This option sends a complete archive to the recipient's PC via GSM modem. A GSM
modem with activated CSD data transfers must be connected either to one of controller COM ports or
to one of I-LB modules connected to the controller via CAN2 bus. The channel address must contain
complete telephone number of the recipient's PC where InteliMonitor is running in Active call receiving
mode.
DATA-ISDN:
This option sends a complete archive to the recipient's PC via ISDN modem. An ISDN
modem must be connected either to one of controller COM ports or to one of I-LB modules connected
to the controller via CAN2 bus. The channel address must contain complete telephone number of the
recipient's PC where InteliMonitor is running in Active call receiving mode.