InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
163
N
OTE
:
The actual setpoint units and range depend on setting of the Power format in
GenConfig.
11.2.1.16
Setpoint: Peak kVA Stop
Group
Process control
Range [units]
Related FW
standard v3.1.0
Force value
possible
YES
Description
If the object apparent consumption (
the power of 2) drops below this setpoint for time longer than
, the gen-set stops automatically (in SPtM application) or gen-set group is
stopped by InteliMains. See also the setpoint
N
OTE
:
The actual setpoint units and range depend on setting of the Power format in
GenConfig.
11.2.1.17
Setpoint: PeakKVAS/S del
Group
Process control
Range [units]
OFF, 1 .. 3200 [s]