InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
164
Related FW
standard v3.1.0
Force value
possible
YES
Description
The setpoints adjusts the delay for automatic Peak kVA start/stop function.
Set 0 (OFF) to disable Peak kVA automatic start function. See also the
setpoints
N
OTE
:
The delay for this function is counted down in any mode if the conditions are
fulfilled (i.e. in OFF when the Mains Import in kVA is higher than
).
11.2.1.18
Setpoint: Export limit
Group
Process control
Range [units]
DISABLED, ENABLED [-]
Related FW
standard v3.1.0
Force value
possible
YES
Description
The setpoint is used to enable and disable the
Export limit
function. If the
function is enabled, the group power is limited so that mains import is always
higher or equal to the setpoint
P
RINCIPLE OF THE EXPORT LIMIT FUNCTION
This function can be used if the setpoint