InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
166
11.2.1.21
Setpoint: TempByPwr int
Group
Process control
Range [units]
0.00 .. 100.00 [%]
Related FW
standard v3.1.0
Description
This setpoint is used to adjust the integration factor for the
Temperature-By-
Power
control loop. See also the setpoints
11.2.1.22
Setpoint: Overheat prot
Group
Process control
Range [units]
DISABLED, ENABLED
Related FW
standard v3.1.0
Force value
possible
YES
Description
The setpoint is used to enable/disable the
Overheat protection
, which is used
for limitation of the group power when there is not enough heat outlet from
the gen-set group to avoid shutdown due to oveheating.
If the
Overheat protection
is enabled and the temperature at the logical
analog input
increases over the setpoint
, the
Temperature-By-
Power
load control loop is temporarily activated to reduce the power
and consequently the temperature.
returns back under the setpoint
, the
Temperature-
By-Power
regulation loop is deactivated and previous load control
mode (e.g. Baseload) takes place.
N
OTE
:
See more information about the
Temperature-By-Power
load control mode in
the description of the setpoint
11.2.1.23
Setpoint: Island enable
Group
Process Control
Range [units]
NO, YES [-]