11.2.3.2
Setpoint: LB/UART Log
Group
Comms settings
Range [units]
DISABLED, ENABLED
Related FW
standard v3.1.0
Force value
possible
YES
Description
The setpoint enables/disables logging of remote communication activity. If
logging is enabled connection and disconnection of each remote terminal as
well as entering access code are recorded into the history.
N
OTE
:
The terminal is disconnected automatically after 5 min of inactivity and next
communication request from the same terminal is considered as a new
connection. When logging is enabled in certain conditions the history may be
filled up with large number of records related to the communication and
important records may be overwritten quite fast.
11.2.3.3
Setpoint: Contr. address
Group
Comms settings
Range [units]
1 .. 32 [-]
Related FW
standard v3.1.0
Description
This setpoint adjusts the address of the particular controller at the CAN2
and/or RS485 bus. Each gen-set connected to the same bus
must have
unique address
.
is in AUT position, the address is assigned
automatically. The setpoint
is preffered then, however if it is in
conflict with other controller present on the CAN2 bus other address will be
assigned to aviod address collision.
N
OTE
:
Address 1 is reccommended for standalone gen-sets.
N
OTE
:
If you are connecting to the controller remotely you have to adjust the proper
controller address in connection settings of the remote client (InteliMonitor,
GenConfig, Modbus client etc.)
N
OTE
:
Address of the controller is also used for Modbus communication via RS485
etc. Address adjusted by this setpoint is therefore universal address of the
controller.