InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
198
controller modifications do not provide the RS232 connector at the COM2
port. The port is redirected to the RS485 interface all the time regardless of
this setpoint.
11.2.3.12
Setpoint: CAN bus mode
Group
Comms settings
Range [units]
32C,8C [-]
Related FW
standard v3.1.0
Description
CAN bus speed selection.
32C: High speed CAN (250 kbps) applicable up to 32 controllers,
CAN bus length limited up to 200 meters.
8C: Low speed CAN (50 kbps) applicable up to 8 controllers, CAN
bus length limited up to 900 meters.
Change of this setpoint is applied after the
controller is switched off and
on again
.
N
OTE
:
Use low speed for long distance connection only. Set all connected
controllers to the same speed.
11.2.3.13
Setpoint: CAN2emptDetect
Group
Comms settings
Range [units]
DISABLED, ENABLED [-]
Related FW
standard v3.1.0
Force value
possible
YES
Description
Enables the detection of missing other controllers on the CAN2 bus. If the
setpoint is in ENABLED position and there aren't any other controllers
detected on the CAN2 bus (the complete bus, not only within the logical
group) the alarm
CAN2Empty
is issued.
11.2.3.14
Setpoint: SHxOcol detect
Group
Comms settings