InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
20
For other controller field wiring terminals
o
Specified tightening torque 0,79Nm (7,0 In-lb)
o
Use only diameter 2,0-0,5mm (12-26AWG) conductor, rated for
75°C minimum.
o
Use copper conductors only.
3.4
Grounding (general)
The shortest possible piece of wire should be used for controller grounding. Use cable min. 2.5 mm
2
.
A brass M4x10 screw with star washer securing ring type grounding terminal shall be used.
The negative “-” battery terminal must be properly grounded.
Switchboard and engine must be grounded at a common point. Use as short a cable as
possible to the grounding point.
3.5
Power supply (general)
To ensure proper function:
Use power supply cable min. 2,5mm
2
Use fuse
o
1 amp for IM-NT
o
2 amps for IM-NT-BB or IM-NTC-BB
Maximal continuous DC power supply voltage is 36VDC.
C
AUTION
!
Switchboard lightning strikes protection according standard regulation is expected!!!
The maximum allowable current through the controller negative terminal is 3 to 8A (depends on the
controller type and binary output load).
H
INT
For more information on technical data regarding supply, inputs, outputs etc. please refer to
3.6
Power supply fusing (general)
Always use according fuse (1Amp or 2Amps) when
connection controller, extension modules or relays to
a power source.
See the diagram for proper fusing.
Binary outputs
Battery 24V DC
-
+
IM-NT
IM-NT-BB
or
IM-NTC-BB
Extension module
T1A or T2A
T2A
T1A