InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
215
threshold for time longer than
N
OTE
:
The mains underfrequency protection is
Mains protection
type - for more
information on protection types please refer to
alarm types section
.
11.2.6.12
Setpoint: Mains f del
Group
Mains protect
Range [units]
0.00 .. 600.00 [s]
Related FW
standard v3.1.0
Description
This setpoints determines the delay for mains under- (defined by
) protections.
N
OTE
:
Although the resolution of this setpoint is 0.01s, in fact the adjusted delay is
rounded to the next higher multiple of the period of the generator voltage.
The period is either 0.02s for 50Hz systems or 0.0166s for 60Hz systems.
E.g. if the delay is set to 0.03s at 50Hz system the real delay will be 0.04s.
11.2.6.13
Setpoint: VectorS prot
Group
Mains protect
Range [units]
DISABLED, PARALLEL ONLY, ENABLED [-]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint selects the function of the built-in vectorshift protection.
DISABLED
The vectorshift protection is disabled.
PARALLEL
ONLY
The vectorshift protection is enabled only while the
both MCB and GCB (and MGCB for applications
with MGCB) are closed.
ENABLED
The vectorshift protection is active always while
the MCB is closed, regardless of the GCB (and
MGCB for applications with MGCB) position.