Description
DISABLED
IM-NT does not provide the AutoSwap functions for other
controllers.
MASTER
At least one controller in the logical group has to be
selected as MASTER if some PriorityAuto Swapping
mode is enabled. Only the controller with lowest CAN
address becomes an active master, the other are ignored
by SLAVE controllers. The MASTER controller evaluates
the Priority changing for all other controllers in the group
and sends them the “forced” Priority values.
11.2.9.4
Setpoint: #SysAMFstrtDel
Group
Pwr management
Range [units]
0 .. 600 [s]
Related FW
standard v3.1.0
Description
System start delay between input
Sys start/stop
closing and start of Power
Management System. When input
Sys start/stop
is controlled by mains
decoupling relay, this setpoint adjusts the delay among the mains failure and
the emergency start of the gen-sets. If the MCB feedback is closed, Power
management is started with 1s delay after the input
Sys start/stop
closing -
parallel operation with the mains.
N
OTE
:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
11.2.9.5
Setpoint: #SysAMFstopDel
Group
Pwr management
Range [units]
0 .. 600 [s]
Related FW
standard v3.1.0
Description
System stop delay between input
Sys start/stop
opening and Power
Management System deactivation. When input
Sys start/stop
is controlled by
mains decoupling relay, this is a delay among the end of mains failure and
opening of GCB. If the MCB feedback is closed, gen-sets are unloaded to
mains prior to GCB opening.
N
OTE
:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.