11.2.9.29
Setpoint: #RunHrsMaxDiff
Group
Pwr management
Range [units]
0 .. 65000 [h]
Related FW
standard v3.1.0
Description
This setpoint adjusts the "deadband" for the
running hours equalization
function. The priorities are swapped not until the relative engine hours (RHE)
difference is higher than this deadband.
N
OTE
:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
11.2.9.30
Setpoint: #PwrBandContr 1
Group
Pwr management
Range [units]
1, 2, 1+2, 3, 1+3, 2+3, 1+2+3 [-]
Related FW
standard v3.1.0
Description
This setpoint is used to select the gen-sets which will run within the power
band #1 if the optimalization according to gen-set size is active. Learn more
about this topis in the chapter
Gen-set size optimalization
.
N
OTE
:
The combinations of gensets must be created so, that the total nominal
power of the Power band #1 < #2 < #3 < #4.
N
OTE
:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
11.2.9.31
Setpoint: #PwrBandContr 2
Group
Pwr management
Range [units]
1, 2, 1+2, 3, 1+3, 2+3, 1+2+3 [-]
Related FW
standard v3.1.0
Description
This setpoint is used to select the gen-sets which will run within the power
band #2 if the optimalization according to gen-set size is active. Learn more