InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
249
11.2.10.3
Setpoint: Phase window
Group
Sync/Load Ctrl
Range [units]
0 .. 90 [°]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint adjusts maximum absolute value of difference between actual
phase angle between the bus and mains voltages for synchronizing.
N
OTE
:
To disable issuing the breaker close command (i.e. for test purpose) adjust
this setpoint to 0. Synchronizing will continue until timeout occurs or the
breaker is closed externally.
N
OTE
:
The setpoint works as a window surrounding the BtoM AngleReq setpoint.
E.g. for BtoM AngleReq = +30° and Phase window = 5°, the breaker closure
is allowed for 25° to +35°.
If you want to lock out the breaker closing during synchronizing control loop
test, set Phase window = 0. This allows the control loop setpoints to be tuned
while actual breaker closing is blocked.