InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
258
Range [units]
0 .. 100 [%]
Related FW
standard v3.1.0
Description
This setpoint adjusts the relative integration factor (I-factor) of the cos-phi
control PI loop. The gain factor (P-factor) for the cos-phi control loop is
adjusted by the setpoint
11.2.12 Group: Force value
11.2.12.1
Setpoint: Force value 1
Group
Force value
Range [units]
[-]
Related FW
standard v3.1.0
Description
This is one of the 16 setpoints reserved for using as alternative setpoints for
the force value functions. The alternative setpoint is to be assigned to a
particular force value function and renamed in GenConfig.
See also the input
N
OTE
:
It is not obligatory to use one of these reserved setpoints for a force value
function. It is possible to use also any other setpoint or value with matching
dimension and decimal resolution.
N
OTE
:
There isn't any relation between the default names of the force value function
blocks, associated binary inputs and the default names of the reserved
setpoints. In other words, the setpoint with default name
Force value 3
is
not
related
to the
Force value 3
function block.
11.2.12.2
Setpoint: Force value 2
Group
Force value
Range [units]
[-]
Related FW
standard v3.1.0
Description
This is one of the 16 setpoints reserved for using as alternative setpoints for
the force value functions. The alternative setpoint is to be assigned to a
particular force value function and renamed in GenConfig.
N
OTE
: