InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
287
11.2.15.2
Setpoint: Alarm only
Group
Act. calls/SMS
Range [units]
DISABLED, ENABLED [-]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint is used to enable sending SMS and/or e-mail alerts when a
"protection" configured as
Alarm only
occurs. See the chapter
Alarm
management
for more information about protection types.
11.2.15.3
Setpoint: Warning
Group
Act. calls/SMS
Range [units]
DISABLED, ENABLED [-]
Related FW
standard v3.1.0
Force value
possible
YES
Force value
possible
YES
Description
This setpoint is used to enable sending SMS and/or e-mail alerts when a
warning
-type protection occurs. See the chapter
Alarm management
for more
information about protection types.
11.2.15.4
Setpoint: Mains protect
Group
Act. calls/SMS
Range [units]
DISABLED, ENABLED [-]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint is used to enable sending SMS and/or e-mail alerts when a
"protection" configured as
Mains protect
occurs. See the chapter
Alarm
management
for more information about protection types.
N
OTE
:
As the
Mains protect
protection does not appear in the alarmlist, the SMS or
e-mail may contain empty alarmlist.