InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
307
12.1.2.8
Value: Bus V L3-L1
Group
Bus values
Units
V
Related FW
standard v3.1.0
Description
Bus voltage phase L3 to L1.
12.1.2.9
Value: Bus V unbal
Group
Bus values
Units
V
Related FW
standard v3.1.0
Description
Bus voltage unbalance. The value is calculated as maximal difference of two
phase voltages at one moment and expressed in % of the bus nominal
voltage.
12.1.2.10
Value: I Aux
Group
Bus values
Units
A
Related FW
standard v3.1.0
Description
This value shows actual current measured at auxiliar terminals.
12.1.2.11
Value: Slip freq
Group
Bus values
Units
Hz
Related FW
standard v3.1.0
Description
Differential frequency between the bus and the mains.
12.1.2.12
Value: Angle
Group
Bus values
Units
°