InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
349
Description
The controller is forced into OFF mode while this input is active. The
controller will return into the previous mode after the input is deactivated.
Use this input if you need to disable the controller temporarily from any
reason (maintenance, control from a higher-level automation system etc..).
Keep in mind that in OFF mode IM-NT automatically closes MCB if there is
healthy Mains.
13.2.1.9
Binary input: REMOTE: Remote MAN
Related FW
standard v3.1.0
Description
The controller is forced into MAN mode while this input is active.
N
OTE
:
Programming of firmware and/or configuration is disabled while this input is
active, as the programming is allowed in OFF mode only and GenConfig is
not able to switch the controller to OFF mode while MAN mode is forced by
this input.
13.2.1.10
Binary input: REMOTE: Remote AUT
Related FW
standard v3.1.0
Description
The controller is forced into AUT mode while this input is active.
N
OTE
:
Programming of firmware and/or configuration is disabled while this input is
active, as the programming is allowed in OFF mode only and GenConfig is
not able to switch the controller to OFF mode while AUT mode is forced by
this input.
13.2.1.11
Binary input: REMOTE: Remote TEST
Related FW
standard v3.1.0
Description
This function is MCB/MGCB specific.
The controller is forced into TEST mode while this input is active. This input
can be used, among others, for following purposes:
In combination with a timer module for periodic testing of the engine.
In combination with the input
start and take over the load by one binary signal (manual switch,
higher-level automation system etc.)