InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
403
14.2.1.28
Binary output: AllAvailGS run
Related FW
standard v3.1.0
Description
The output closes if all gen-sets available to take part in PMS are running
and loaded. All gen-sets having the same logical group (
Control group
) as
this controller has are cons gen-sets from other logical groups if
those are currently linked with controller’s logical group (using
group link
function
).
14.2.1.29
Binary output: Common Wrn
Related FW
standard v3.1.0
Description
The output is closed while there is at least one alarm of the
Warning
type
present in the alarm list. The alarm can be in any state, i.e. active
unconfirmed, active confirmed or inactive unconfirmed. See the chapter
Alarm management
for more information.
14.2.1.30
Binary output: Common Fls
Related FW
standard v3.1.0
Description
The output is closed while there is at least one alarm of the
Sensor fail
type
present in the alarm list. The alarm can be in
any state
, i.e. active
unconfirmed, active confirmed or inactive unconfirmed.See the chapter
Alarm
management
for more information.
14.2.1.31
Binary output: Common Al
Related FW
standard v3.1.0
Description
The output is closed while there is at least one alarm of the
Alarm only
type
present in the alarm list. The alarm can be in any state, i.e. active
unconfirmed, active confirmed or inactive unconfirmed. See the chapter
Alarm management
for more information.
14.2.1.32
Binary output: Common Hst
Related FW
standard v3.1.0
Description
The output is closed for 1s when any alarm of
History record
type appears.
See the chapter
Alarm management
for more information.