InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
431
SHAIN
-
-
4
-
Shared (virtual) Analog Input module
2
SHAOUT
-
-
-
4
Shared (virtual) Analog OUTput
module
2
PLC
x
x
x
x
Programmable (internal) logic module.
1
N
OTE
:
Maximum number of configured modules (both extension and virtual) is given by available addresses.
The numbers in the table are valid in the case that no other modules are configured.
15.2 Table of analog input functions
15.2.1.1
Analog input: MLC:AnExSysBld
Related FW
standard v3.1.0
Description
This input is used for external determination of system load.
15.2.1.2
Analog input: MLC:AnExI/E
Related FW
standard v3.1.0
Description
This functional input is used for requesting the
mains import
value externally
by an analog input. The setpoint
position.
15.2.1.3
Analog input: MLC:TByPwr
Related FW
standard v3.1.0
Description
This functional input is used as the temperature input into the load control
loop if the loop is switched into "T BY PWR" position. More information is
available at the setpoint
15.2.1.4
Analog input: MPF:AnExI/E
Related FW
standard v3.1.0
Description
This functional input is used for requesting the
mains cos phi factor
externally by an analog input. The setpoint
PF-IM/EX position.
The analog value is transformed to the requested cos phi factor following
way: