InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
56
F
UNCTION
N
AME
(
ALPHABETICAL
ORDER
)
B
RIEF
D
ESCRIPTION
R
ELATED
S
ETPOINTS
,
I
NPUTS AND
O
UTPUTS
User MODBUS
Modbus registers (up to 128) can be
defined for every value and setpoint in
the controller. This can be used to
prevent shift of Modbus numbers, to
standardize Modbus communication for
several applications or to make Batch
reading and writing much more user
friendly. For more information on Modbus
please refer to the Communication Guide
or to the context help in GenConfig.
Variable
connection of
devices on CAN
bus
It is possible to select number and type
of devices connected on CAN2 bus
(MODEM: I-LB+ or OTHER: InteliVision,
I-RD). CAN addresses 123 and 124 are
always dedicated to connection of
OTHER devices (e.g. InteliVision 5
CAN). Using two setpoints dedicated to
this function, it is possible to choose if
addresses 122 and 125 are used for
communication by OTHER devices or in
MODEM mode (i.e. prepared for I-LB+ or
IB-NT connection).
CANAddrSwitch1
CANAddrSwitch2
Voltage
protections
mode Ph-N or
Ph-Ph
In the controller it is possible to select
whether fixed protections are based on
measured Ph-N voltage or on measured
Ph-Ph voltage. For more information of
fixed protections please refer to the
separate chapter Protections and Alarm
management.
FixVoltProtSelect
Wrong Phases
sequence
Controller automatically detects if phases
measurement is connected in wrong
sequence (note that the wrong sequence
is not detected if the phases are just
rotated, i.e. L2-L3-L1)
W
RONG
P
H
S
EQ