InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
64
I
SLAND
ENABLE
P
ARALLEL
ENABLE
S
YNCHRO
ENABLE
MFS
TART
MGCB
PARAL
C
LOSE
S
HORT
D
ESCRIPTION
NO
YES
NONE
NO
MCB CLOSED
- Parallel operation is possible.
- Transfer with synchronization via InteliMains is
N/A
- Gen-sets will not be started when the Mains
fails.
- Gen-sets will synchronize directly to the Mains
(MGCB already closed), i.e. synchronization
transfer from Mains to Parallel
- MGCB will be closed if the MCB is closed
7.3.2
MCB
I
SLAND ENABLE
P
ARALLEL
E
NABLE
S
YNCHRO ENABLE
MFS
TART
S
HORT
D
ESCRIPTION
YES
YES
REVERSE
YES
Island and Parallel operation is
possible.
Transfer with synchronization via
InteliMains is possible
Gen-sets will be started when the
Mains fails.
YES
YES
REVERSE
NO
Island and Parallel operation is
possible.
Transfer with synchronization via
InteliMains is possible
Gen-sets will not be started when the
Mains fails.
YES
YES
NONE
YES
Island and Parallel operation is
possible. (Controller can transfer to
Parallel operation from Mains
operation.)
Transfer with synchronization via
InteliMains is not possible
Gen-sets will be started when the
Mains fails.
YES
YES
NONE
NO
Island and Parallel operation is
possible. (Controller can transfer to
Parallel operation from Mains
operation.)
Transfer with synchronization via
InteliMains is not possible
Gen-sets will not be started when the
Mains fails.
YES
NO
NONE
YES
Island operation is possible.
Transfer with synchronization via
InteliMains is not possible
Gen-sets will be started when the
Mains fails.