If the reactive power is measured, then the measurement method should
match the method used for active power measurement, i.e. if the setpoint
is set to CT INPUTS, the
ANALOG INPUT and vice versa. If the setting differs, the measurement for
both active and reactive power are both taken from CT input. Setting NONE
can be used in any combination without changing the setting of the second
measurement.
11.2.1.12
Setpoint: PeakLevelStart
Group
Process control
Range [units]
Related FW
standard v3.1.0
Force value
possible
YES
Description
If the object consumption (
) exceeds this setpoint for time longer
, the gen-set group is started. Adjusting the
to 0 (OFF) disables the autostart. See also the setpoint
N
OTE
:
The IM-NT output
must be connected to the inputs
Sys
Start/Stop
of all controllers in the group. This can be done either physically by
wires or by CAN bus using shared peripherial modules. See the GenConfig
help for more information about shared modules.
11.2.1.13
Setpoint: PeakLevelStop
Group
Process control
Range [units]
Related FW
standard v3.1.0
Force value
possible
YES
Description
If the object consumption (
) drops below this setpoint for time longer
, the gen-set group is stopped (if there isn't any other
reason to keep the group running, such as binary input
). See
also the setpoint