InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
179
Range [units]
10 .. 30000 [V]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint is used to adjust the nominal bus voltage (phase to neutral). If
you do not know the phase-neutral nominal voltage, you can adjust the
phase-phase nominal voltage
. The controller will then
recalculate the phase-neutral nominal voltage automatically.
N
OTE
:
The actual setpoint units and range depend on setting of the Power format in
GenConfig.
N
OTE
:
If different voltage on Mains and on Bus is required the following procedure is
required:
Both setpoints (
) must be adjusted to the same
values according to the value of actual Bus nominal voltage. E.g. Bus
nominal is 231 V but Mains nominal is 240 V.
In this case both setpoints need to be adjusted to 231 V and setpoints of
corresponding protections for Mains need to be set assymetrically.
For 240 V on Mains it is typical to open MCB when voltage reaches 254 V or
225 V. Since the setpoint is adjusted to 231 V corresponding protection
setpoints need to be adjusted to
the desired values are reached).
11.2.2.8
Setpoint: BusNomVph-ph
Group
Basic settings
Range [units]
17 .. 60000 [V]
Related FW
standard v3.1.0
Description
This setpoint is used to adjust the nominal bus voltage (phase to phase). This
setpoint is also recalculated automatically when the phase-neutral nominal
voltage
This setpoint can be used if you know the phase-phase nominal voltage only.
The controller will recalculate the phase-neutral nominal voltage
automatically when this setpoint is changed.
N
OTE
:
The actual setpoint units and range depend on setting of the Power format in
GenConfig.
N
OTE
:
If different voltage on Mains and on Bus is required the following procedure is