InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
200
OTHER
The address is used for direct connection to any other device
as e.g. IV8 or I-RD
11.2.3.17
Setpoint: CANnegotiation
Group
Comm settings
Range [units]
OFF, AUT [-]
Related FW
standard v3.1.0
Description
This setpoint defines if CAN address is used in the standard way or CAN
addresses are reconfigured internally.
OFF
The control unit has the same address which is necessary for
communication. The address can be changed only from
InteliMonitor or controller screen.
AUT
Controllers can change their addresses when are interconnected
via CAN2 bus to prevent CAN bus collision. Controller address is
set up to different address if another unit with the same address
is detected on the CAN bus.
C
AUTION
!
Make sure all controllers have this setpoint set to AUT. It does
not work properly if there are controllers with this setpoint
adjusted to OFF and others with AUT setting.
C
AUTION
!
This function is not designed to cooperate with controllers which
do not support it. Make sure it is adjusted to OFF if there are
other controllers on the CAN without this setpoint.
11.2.3.18
Setpoint: IP Addr mode
Group
Comms settings
Range [units]
[-]
Related FW
standard v3.1.0
Description
The setpoint is used to select the method how the ethernet connection is
adjusted.