This setpoint adjusts the delay for battery
alarms.
11.2.6 Group: Mains protect
11.2.6.1
Setpoint: Mns2POvrldProt
Group
Mains protect
Range [units]
DISABLED, ENABLED [-]
Related FW
standard v3.1.0
Force value
possible
YES
Description
Enables or disables the mains overload (IDMT) protection. This protection is
evaluated with variable delay. For more information see setpoint
11.2.6.2
Setpoint: OverldStrtEval
Group
Mains Protect
Range [units]
100 .. 200 [%]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint specifies the power level relative to the
, where
the mains overload (IDMT) protection starts to be evaluated. See the setpoint
for more information about the mains overload (IDMT)
protection.
11.2.6.3
Setpoint: 2POvrldStEvDel
Group
Mains Protect
Range [units]
0.0 .. 600.0 [s]
Related FW
standard v3.1.0
Description
This setpoint adjusts the reaction time of the mains overload (IDMT)
protection if the load level is 200% of the base level given by the setpoint