InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
212
11.2.6.5
Setpoint: Mains2Inom del
Group
Mains protect
Range [units]
0.0 .. 60.0 [-]
Related FW
standard v3.1.0
Description
This setpoint adjusts the reaction time of the IDMT overcurrent protection if
the overcurrent level is 200% of the
The reaction time of the IDMT overcurrent protection is not fixed; it depends
on how much is the actual current above the limit (nominal). The higher is the
overcurrent the shorter the reaction time will be.
E
XAMPLE OF
IDMT
OVERCURRENT PROTECTION CURVE
N
OTE
:
When the IDMT protection is activated the MCB is opened and the event is
recorded in the Alarmlist and History. The further MCB closing is blocked
until Fault Reset has been pressed to clear the alarm.
11.2.6.6
Setpoint: Mains >V MP
Group
Mains protect
Range [units]