used in some situations to allow genset start after Sys Start/Stop gets active.
It is not destined for normal operation. Please refer to the Troubleshooting
guide for more information (chapter "MGCB is not closed although gensets
are running").
N
OTE
:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
11.2.9.13
Setpoint: #LoadResStop 4
Group
Pwr Management
Range [units]
Related FW
standard v3.1.0
Description
This setpoint is used to adjust the load reserve for stop in absolute mode. i.e.
= ABS (kW) or ABS (kVA) if the reserve set #4 is active.
Learn more about reserves in the chapter
Reserves, minimal running power
.
The currently active reserve set is selected by binary inputs
. If none of these inputs is active the set #1 is selected.
N
OTE
:
The reserve for stop must be always adjusted higher than the reserve for
start.
N
OTE
:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
11.2.9.14
Setpoint: #%LdResStrt 1
Group
Pwr Management
Range [units]
Related FW
standard v3.1.0
Description
This setpoint is used to adjust the load reserve for start in relative mode. i.e.
= REL (%) if the reserve set #1 is active. Learn more about
reserves in the chapter
Reserves, minimal running power
.
The currently active reserve set is selected by binary inputs
. If none of these inputs is active the set #1 is selected.