11.2.13.3
Setpoint: Ld shed mode
Group
Load shedding
Range [units]
PWR ONLY, FRQ ONLY [-]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint adjusts which type of load shedding is active. When PWR
ONLY is selected the load shedding is based on active power. If FRQ ONLY
is selected the load shedding is based on frequency.
N
OTE
:
Learn more about load shedding in the separate chapter
Load shedding
.
11.2.13.4
Setpoint: Ld shedStages
Group
Load shedding
Range [units]
1 .. 3 [-]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint adjusts the number of load shedding stages that are used in
load shedding.
E
XAMPLE
:
If 1 load shedding stage is selected the controller will perform one load
shedding stage and rest of the load shedding stages will be omitted.
11.2.13.5
Setpoint: Ld shedLevel1
Group
Load shedding
Range [units]
Related FW
standard v3.1.0