InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
341
12.1.17 Group: Statistics
12.1.17.1
Value: Sum MWh
Group
Statistics
Units
MWh
Related FW
standard v3.1.0
Description
In BTB - this value shows always 0.
This value shows the total sum of MWh counted from all the genset in the
according control group. If two separate control groups are connected by
group link this value shows sum of MWh from both connected control groups.
N
OTE
:
The counter can be readjusted/reset from InteliMonitor menu Monitor -> Set
statistics.
12.1.17.2
Value: Sum MVAhr
Group
Statistics
Units
-
Related FW
standard v3.1.0
Description
In BTB - this value shows always 0.
This value shows the total sum of MVAhr counted from all the genset in the
according control group. If two separate control groups are connected by
group link this value shows sum of MVAhr from both connected control
groups.
N
OTE
:
The counter can be readjusted/reset from InteliMonitor menu Monitor -> Set
statistics.
12.1.17.3
Value: M kWh I
Group
Statistics
Units
kWh
Related FW
standard v3.1.0
Description
This value shows the sum of kWh imported from the mains.