InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
346
SHAIN
-
-
4
-
Shared (virtual) Analog Input module
2
SHAOUT
-
-
-
4
Shared (virtual) Analog OUTput
module
2
PLC
x
x
x
x
Programmable (internal) logic module.
1
N
OTE
:
Maximum number of configured modules (both extension and virtual) is given by available addresses.
The numbers in the table are valid in the case that no other modules are configured.
13.2 Table of binary input functions
13.2.1.1
Binary input: MCB feedback
Related FW
standard v3.1.0
Description
This input is used for connection of the normally open feedback contact from
the mains circuit breaker or contactor. If the input is active, the controller will
consider the MCB as closed and vice versa.
If the feedback does not respond to a change of the control output
MCB Fail
will be issued.
If the feedback indicates the MCB has unexpectedly closed without
any command given by the control output, the alarm
MCB Fail
will be
issued immediately.
If the feedback indicates the MCB has unexpectedly opened without
any command given by the control output, the controller will accept
this situation and the following behavior will depend on mains
conditions (healthy or failure).
13.2.1.2
Binary input: MCB feedback
Related FW
standard v3.1.0
Description
This input is used for connection of the normally open feedback contact from
the mains circuit breaker or contactor. If the input is active, the controller will
consider the MCB as closed and vice versa.
If the feedback does not respond to a change of the control output
MCB Fail
will be issued.
If the feedback indicates the MCB has unexpectedly closed without
any command given by the control output, the alarm
MCB Fail
will be
issued immediately.
If the feedback indicates the MCB has unexpectedly opened without
any command given by the control output, the controller will accept
this situation and the following behavior will depend on mains
conditions (healthy or failure).