358
13.2.1.35
Binary input: StartButton
Related FW
standard v3.1.0
Description
This input is used for an external START button mounted on the switchboard.
The function of the input is identical as function of the start button on the
controller front panel.
The input is enabled only if the setpoint
EXTBUTTONS or BOTH.
13.2.1.36
Binary input: StopButton
Related FW
standard v3.1.0
Description
This input is used for an external STOP button mounted on the switchboard.
The function of the input is identical as function of the stop button on the
controller front panel.
The input is enabled only if the setpoint
EXTBUTTONS or BOTH.
13.2.1.37
Binary input: MCBButton
Related FW
standard v3.1.0
Description
This input is used for an external MCB button mounted on the switchboard.
The function of the input is identical as function of the MCB button on the
controller front panel.
The input is enabled only if the setpoint
EXTBUTTONS or BOTH.
13.2.1.38
Binary input: GroupLink
Related FW
standard v3.1.0
Description
This input can be mainly used in BTB application. Nonetheless, any IM-NT or
IGS-NT controller can be used for group link function even if bus tie breaker
is controlled manually or by third party device (only proper feedback from
BTB is required).
If this input is configured, the group linking function is active, i.e. this
controller becomes the status server for two groups of gen-sets and informs
them about the BTB status. Closing of this input indicates closing of BTB (i.e.
two groups are linked together). Opening of this input indicates opening of
BTB (i.e. two groups are working separately).
N
OTE
:
This input is intended for connecting to the BTB feedback.