Description
This input is used to switch the
IG-NT built-in
terminal (display) to the
alternative backlight intensity mode (e.g. "night mode"). The alternative
intensity level is adjusted using the display buttons (see the operator guide
for details) while this input is active and is stored in the nonvolatile memory.
N
OTE
:
A binary input with identical function (not configurable) is located in the power
connector of the external IG-Display and IS-Display modules.
13.2.1.42
Binary input: PulseCounter 1
Related FW
standard v3.1.0
Description
This is the input of the
PulseCounter #1
module. The module counts pulses
at the input and if the input pulses counter reaches value given by the
setpoint
, the counter value
Statistic
) is increased by 1 and input pulses conter is reset to 0. Both counter
value and input pulses counter are stored in the nonvolatile memory.
The
PulseCounter
modules are intended e.g. for connecting external energy
or fuel meters with pulse outputs.
N
OTE
:
Minimal pulse width as well as minimal pause between two succesive pulses
is 100ms.
N
OTE
:
The counter value can be reset in the InteliMonitor statistics window.
13.2.1.43
Binary input: PulseCounter 2
Related FW
standard v3.1.0
Description
This is the input of the
PulseCounter #2
module. The module counts pulses
at the input and if the input pulses counter reaches value given by the
setpoint
, the counter value
Statistic
) is increased by 1 and input pulses conter is reset to 0. Both counter
value and input pulses counter are stored in the nonvolatile memory.
The
PulseCounter
modules are intended e.g. for connecting external energy
or fuel meters with pulse outputs.
N
OTE
:
Minimal pulse width as well as minimal pause between two succesive pulses
is 100ms.
N
OTE
:
The counter value can be reset in the InteliMonitor statistics window.