InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
402
14.2.1.22
Binary output: Syst res OK
Related FW
standard v3.1.0
Description
The output is closed while the
actual reserve
is above the
selected reserve
for start.
14.2.1.23
Binary output: Syst res 1 OK
Related FW
standard v3.1.0
Description
The output is closed while the
actual reserve
is above the reserve for start
from the
reserve set #1
.
14.2.1.24
Binary output: Syst res 2 OK
Related FW
standard v3.1.0
Description
The output is closed while the
actual reserve
is above the reserve for start
from the
reserve set #2
.
14.2.1.25
Binary output: Syst res 3 OK
Related FW
standard v3.1.0
Description
The output is closed while the
actual reserve
is above the reserve for start
from the
reserve set #3
.
14.2.1.26
Binary output: Syst res 4 OK
Related FW
standard v3.1.0
Description
The output is closed while the
actual reserve
is above the reserve for start
from the
reserve set #4
.
14.2.1.27
Binary output: GSG params OK
Related FW
standard v3.1.0
Description
The output is closed if bus electric values are in limits and there is a sufficient
number of loaded gen-sets that do not have 2nd level alarm active (this
output is closed regardless of 1st level alarms on gen-sets). For more
information on alarm types please refer to
Alarms and protections chapter
.