InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
409
14.2.1.58
Binary output: MODES: Man mode
Related FW
standard v3.1.0
Description
The output is closed while the controller is currently in MAN mode (either
switched by the mode selector on the front panel or by the input
).
14.2.1.59
Binary output: MODES: Aut mode
Related FW
standard v3.1.0
Description
The output is closed while the controller is currently in AUT mode (either
switched by the mode selector on the front panel or by the input
14.2.1.60
Binary output: MODES: Test mode
Related FW
standard v3.1.0
Description
The output is closed while the controller is currently in TEST mode (either
switched by the mode selector on the front panel or by the input
14.2.1.61
Binary output: MainsParams OK
Related FW
standard v3.1.0
Description
This output indicates that the mains is healthy. The output is closed while
all
mains electrical parameters
are in limits. If MCB is closed, the output
deactivates after the the delay for fixed voltage or frequency protections
elapses. If MCB is opened, the output deactivates immediately after electrical
parameters get out of limit (e.g. frequency, voltage, voltage unbalance etc.).
14.2.1.62
Binary output: Bus Params OK
Related FW
standard v3.1.0
Description
This output indicates that the bus is healthy. The output is closed while
all
bus electrical parameters
are in limits.
14.2.1.63
Binary output: TimerAct 1-4
Related FW
standard v3.1.0
Description
This is combined output from timer channels 1-4. The output is closed if at