InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
415
or PLC modules inputs) where a binary value is required, however it has to
be continously inactive.
14.2.1.81
Binary output: Logical 1
Related FW
standard v3.1.0
Description
This output is always closed. It may be used in functions (e.g. ECU outputs
or PLC modules inputs) where continuously active binary value is required.
14.2.1.82
Binary output: PeriphCommErr
Related FW
standard v3.1.0
Description
The output is closed while there is an error in the communication with any
peripheral unit (e.g. IS-AIN8, IGS-PTM, ...).
14.2.1.83
Binary output: WrongPhSeq
Related FW
standard v3.1.0
Description
Binary output WrongPhSeq is active when at least one of the following
conditions is fulfilled: Mains/Bus phase is inverted or wrong mains/bus phase
sequence or opposed mains/bus phase sequence is detected.
14.2.1.84
Binary output: User Button 1
Related FW
standard v3.1.0
Description
This output can be specified for example on buttons on IV-5/8 or in SCADA
diagram in InteliMonitor. Its state depends on function assigned to the related
button.
It is possible to lock UserButton commands in configuration to specific user
level. Buttons 1-8 and 9-16 are locked separately.
ON
Pressing the button changes the state of log. binary output
User Button X to closed. When the output is closed and the
button is pressed state is not changed.
OFF
Pressing the button changes the state of log. binary output
User Button X to opened. When the output is opened and
the button is pressed state is not changed.