InteliPro, SW version 1.4,
©
ComAp
–
April 2014
InteliPro 1.4 Comprehensive Guide - rev. 1
4-15
CB1 Protection
The output is normally energized for the complete duration of the unit operation. It de-energizes
immediately after CB1 Feedback goes from activated position to zero. It keeps de-activated for Basic
settings: CB1 Prot Timer.
CB2 Protection
The output is normally energized for the complete duration of the unit operation. It de-energizes
immediately after CB2 Feedback goes from activated position to zero. It keeps de-activated for Basic
settings: CB2 Prot Timer.
Self Test
This input indicates normal operation of the unit.
the output is closed:
-
after power-up of the unit, when the SW application starts successfully and watchdog was not
detected.
-
If the watchdog was detected, the watchdog alarm is set. In this case, the output closes only
after fault reset, when the watchdog alarm is cleared.
-
when the auxiliary voltage is restored over Aux Low level state.
the output is open:
-
when power fail is detected (low auxiliary voltage even)
-
in case of watchdog reset
-
when the unit is being programmed
-
when the unit is switched off
Mains OK
This output indicates that the mains is healthy. The output is closed while all mains electrical
parameters are in limits. The output deactivates immediately as soon as any of the mains protections
is activated. As soon as all mains parameters are in limits again, the output closes immediately.
Avg V Prot
The output activates in case that average overvoltage protection is activated.
Pole Slip Prot
The output activates in case that the pole slip protection is activated.
Dyn Volt Prot
The output activates in case that the dynamic voltage protection is activated.
AL AIx Wrn/Trp, AL IOM AIx Wrn/Trp
The outputs are available to indicate warning or trip, caused by any of the analog inputs on InteliPro
unit, or on IOM extension module, where "x" marks the number of the analog input. The output is
activated in the moment when the appropriate AI warning/trip event is issued and stays activated until
the alarm message disappears from the alarm list.
AL Aux Volt
The output activates in case of the Warning-type alarm of the power supply over- or undervoltage.
AL Common Wrn
The output activates in case of any Warning-type alarm.
AL Common Fls
The output activates in case of any sensor-fail on the analog inputs.